Differentiation time constants (delay time) for regulators
The delay time can be given in two formats:
In the range of 0.00 to 99,99 s or from 0:01 min up to 99:99 min.
The differentiation portion is updated at a rate according to the set time. When Td = 0, no Dif-
ferentiation portion is calculated.
(possible entries: 00.00 sec to 99:99 min)
[Yx %]
Maximum control output for regulator
The displayed control output Ys can be limited to a maximum value of < 100 %. A negative
entry of the control output limit at reverses the direction that it operates.
(possible entries: -100 % to +100 %)
5)
The response time t
[t90 ]
Longer response times can be useful when the measurement value fluctuates rapidly.
Response times: (OFF; 0.01, 0.05, 0.25, 1.00, 3.00 or 10.00 sec)
5)
The measurement signal can be stored as a maximum value. Hold times for the maximum
[tClr]
value can be set to:
(OFF; 0.01, 0.5, 0.25, 1.00, 5.00 or 25.00 sec; Etrn (external); Auto)
When set to OFF the hold time is switched off and the current value is always displayed.
(For a description of hold time see 6.4. Operating the InfraWin PC Program)
Switching minimum value / maximum value hold
[MnMx]
„1 " = maximum value; „–1 " = minimum value
[°C/°F]
Switching the display from °C <=> °F
Switching the display will only convert the display functions of the DA 6000, i.e. there is no
conversion of the calculations from the connected pyrometer. This can then result in rounding-
up errors during the transmission of parameters that contain temperature values.
[baud]
Baud rate of the serial interface
The transmission speed of the interface can be set to the following values:
1200 Bd, 2400 Bd, 4800 Bd, 9600 Bd, 19.2 kBd and 38.4 kBd.
[addr]
Serial interface Addresses for connected pyrometers (00 to 97):
(Just in online-mode of the pyrometer)

5.2.1. Special displays

[A00?]
Search display, until the DA 6000 has located a digital pyrometer at its interface. The Baud rate
...
is displayed on the main display, and the tested address on the menu display.
[A30?]
Temporary display, which follows an attempt to set a parameter value, that is outside the per-
[-no-]
missible limits.
Temporary display which follows an attempt to change a parameter setting of a pyrometer when
[off-]
it is in the offline operating mode.
Temporary display by changing from address or baud rate.
[Wait]
[thEr]
Waiting on temperature of Thermostat
[ChoP]
Chopper-controls still in preparation
3)
Only for pyrometers with PID regulator
4)
As yet only for IN 5 plus; IN5/5 plus
5)
It also takes effect first
of the measurement signal can be adjusted using a low-pass filter.
90
OFF = own time constant of the Pyrometer (see specification sheet)
The response time t
[t90 ].
3)
3)
4)
always has to be smaller than the set reset time.