Herunterladen Inhalt Inhalt Diese Seite drucken

External Battery Cabinet Installation - Sola Hevi Duty S3K2U series Handbuch

Inhaltsverzeichnis

Werbung

5.4

External Battery Cabinet Installation

Optional Sola/Hevi-Duty external battery cabinets may be connected to the UPS to provide additional
battery run time. External battery cabinets are designed to be placed all on one side of the UPS or
stacked beneath the UPS. The run time is limited to a maximum of four (4) hours.
CAUTION
!
The external battery cabinet(s) are heavy (see 12.0 - Specifications (Sechnische Daten)).
External battery cabinets can be used in rack-mount or tower configuration. Take proper
precautions when lifting them.
VORSICHT
!
Externe Batteriegehäuse sind schwer (siehe 12.0 - Technische Daten). Externe
Batteriegehäuse können in einer Gestellmontage- oder Turmkonfiguration eingesetzt werden.
Ergreifen Sie die entsprechenden Vorsichtsmaßnahmen, wenn sie gehoben werden müssen.
1. Visually inspect the external battery cabinet for freight damage. Report damage to the carrier
and your local distributor, Sola/Hevi-Duty Representative or Sola/Hevi-Duty Technical Services.
2. The rack-mount handles are shipped with the external battery cabinet and may be installed at
this time (see 5.3 - Rack-Mount UPS Conversion and Installation).
3. Fixed rails and securing hardware ship with the external battery cabinet. Fasten the fixed rails
into position with the screws per the instructions included with the UPS. Repeat
Steps 1 through 10 from 5.3 - Rack-Mount UPS Conversion and Installation.
4. Use the support bases included with the UPS for the tower option to prevent tip-over. One
additional set of support base spacers ships with each external battery cabinet.
5. Connect the supplied external battery cabinet cable to the rear of the external battery cabinet,
then to the rear of the UPS, as shown at right.
6. The UPS is now equipped with additional backup battery run time. For approximate battery run
times, refer to Table 6 - Battery run times.
1
2
3
4
INTELLISLOT
BATTERY
CONNECTOR
INPUT
BREAKER
PUSH TO RESET
INPUT
BATTERY
CONNECTOR
OUT
IN
LOAD 1
PHONE / FAX / MODEM / NETWORK
PROTECTION
LOAD 2
17
Installation
BATTERY
CONNECTOR
1440VA/DC 48V/30A
1000VA/DC 48V/20A
+
-

Werbung