5.0
I
NSTALLATION
5.1

Preparation

1. Visually inspect the UPS for freight damage. Report damage to the carrier and your local
distributor, Sola/Hevi-Duty representative or Sola/Hevi-Duty Technical Services.
CAUTION
!
The UPS is heavy (see Table 5 - Battery cabinet specifications). Take proper precautions
when lifting or moving it.
2. Decide where to place the S3K2U. Install the UPS indoors in a controlled environment where it
cannot be accidentally turned Off. Place it in an area of unrestricted airflow around the unit,
away from water, flammable liquids, gases, corrosives, and conductive contaminants. Maintain a
minimum clearance of 100mm (4 inches) in the front and rear of the UPS. Maintain an ambient
temperature range of 0°C to 40°C (32°F to 104°F).
NOTE
UPS operation in temperatures above 25°C (77°F) reduces battery life.
3. The S3K2U may be installed in either a tower configuration or in a rack, depending on available
space and use considerations. Determine the type of installation and follow the appropriate
instructions in either Tower UPS Installation or Rack-Mount UPS Conversion and

Installation.

5.2

Tower UPS Installation

When using the S3K2U in a tower configuration, use the included support base (shown below, left) to
stabilize the UPS. If two or more battery cabinets are added, the spacers—included with the battery
cabinets—should be used to accommodate the additional cabinets.
Figure 6

Support base for tower configuration

Tower Stand - Fully Extended
Spacers Can be Added to Accommodate External Battery Cabinets
1. To orient the display for vertical viewing, remove the front plastic bezel by pulling forward evenly
on both sides.
2. Peel the backing from the vertical display overlay and apply to the existing display.
3. Snap the front bezel back into place.
5.3

Rack-Mount UPS Conversion and Installation

NOTE
When rack mounted, the UPS must be supported by a shelf, slide rails, brackets or fixed rails
on each side. The rack mount handles WILL NOT support the weight of the UPS. They are
used to move the UPS into and out of the rack.
1. For fixed rail installations, install the rack mount handles using four (4) M4x6 screws (see
Figure 7).
Connectors Snap into Slots on Base
12
Installation