Herunterladen Inhalt Inhalt Diese Seite drucken

Rack Mount Handles; Fixed Rails With Inner Members Extended - Sola Hevi Duty S3K2U series Handbuch

Inhaltsverzeichnis

Werbung

Figure 7

Rack mount handles

Two (2) M4x6
Flat Head Screws
2. Unpack the two fixed rail assemblies and mounting hardware. Loosen the wing nuts and extend
the inner members to their outermost position (see Figure 8).
Figure 8

Fixed rails with inner members extended

CAUTION
!
Reduce the risk of tipping the rack enclosure by placing the UPS or battery cabinet in the
lowest possible rack position.
3. Determine the height position inside the rack enclosure where you want to mount the UPS or
battery cabinet. Make sure fixed rails are at the same mounting height on each of the four (4) rack
mounting rails.
4. Attach the two (2) fixed rails to the racks mounting rails. The fixed rail assemblies fit on the
inside of the rack mounting rails.
5. Insert two (2) M5 flat head screws loosely (finger-tight) into the top and bottom holes on the front
of the fixed rail assembly (see Figure 9).
6. Extend fixed rail by sliding inner member backward until it touches the rear rack mounting rail.
7. Insert two (2) M5 screws loosely (finger-tight) into top and bottom holes on the rear of the fixed
rail assembly.
8. Check alignment of fixed rails and tighten all screws to ensure locking action.
Rack Mount Handles
Wing Nuts for
Adjustment
Adjustable Length
Maximum 800 mm
Minimum 485 mm
13
Installation
Two (2) M4x6
Flat Head Screws
M4x6 Flat Screw
Adjustable Slide
Assembly

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis