True RMS AC Flexible Clamp Meter 3000 A / English
3. Description
Meter Description
1. Flexible current coil
2. Range switch
3. Power switch
4. Analog voltage output cable
5. Power indication
6. Turn knob
4. Specifications
Function
Range
Measurement Range
30 A ac
0.30 A to 30 A
AC Current
50 - 400Hz
300 A ac
30 A to 300 A
True RMS
3000 A ac 300 A to 3000 A
Note: Accuracy is given as ±(% of reading + counts of least significant digit) at 23°C
±5°C, with relative humidity less than 80%RH. The measured conductorbis placed in the
center of the coil.
Output Noise: <5.5 mV for each range.
Max. output voltage: 5.8 V. If the output voltage is greater than 3 V, the results indicate
that the measurement has been out of range and not to be used as indicator assessment.
2
Output Voltage Accuracy
100 mV/A
±(3.0% + 5 mV)
10 mV/A
±(3.0% + 3 mV)
1 mV/A
±(3.0% + 3 mV)
02/01/2018 Version No. 001
True RMS AC Flexible Clamp Meter 3000 A / English

5. General Specifications

Power indication
Green LED light
Low Battery indication
Red LED light
Operating Temperature
41°F to 104°F (5°C to 40°C)
Storage Temperature
- 4°F to 140°F (-20°C to 60°C)
Operating Humidity
Max 80% up to 87°F (31°C) decreasing linearly to 50% at
104 °F (40°C)
Storage Humidity
<80%
Operating Altitude
7000 ft. (2000 meters) maximum.
Battery
1. 5 V "AAA" Size Battery x 2
Safety Standard
EN61010-1, EN61010-2-032, EN61326-1. Overvoltage
Category III 1000V and Category IV 600 V, Pollution
Degree 2

6. Operation

6-1 AC Current Measurements
Turn on the instrument power supply, insert the output line of the meter into the input
end of the high precision digital universal meter with AC voltage measurement function.
Pre-estimate the size of the current to obtain the best output signal and choose a good
measurement of gear. Single phase and then measured the ring into the flexible coil,
placed in the central position, and completely closed. This can be converted to obtain the
magnitude of the current value.