UPSI-IP-1 series | UPSI- IP-2 series
20 Software
Parameter
Value / unit
adjustable
Load Sensor
100mA...800mA
in steps of mA
Shutdown
1s...3600 s
System after
in steps of seconds
Maximum
1s...3600 s
Backup Time
in steps of seconds
Need capacity
1%...100%
before power up
in steps of 1%
Ignition Timer
Restart Delay
1s...180 s
in steps of seconds
Description
A shortfall of this current value leads to the assumption that
the connected system is shut down. Thereupon the system
will be separated for x seconds (restart delay) for running
the reboot function, in case input voltage has returned.
Concerns the hold-up time: During this time, the supply of
the system is maintained. After this time has expired and
the input supply is still missing, the shutdown process of
the PC gets started. If the voltage returns at the grid side
within this time there will be no action.
The maximum hold-up time. After this time the application
will be disconnected. This setting can be used for systems
which do not need a shut down process or in case the
application hangs up and has to be disconnected abruptly.
Minimum capacity for release of UPS. Hereby can be
secured that the application can safely be powered at a
power fail. As a result, the switch-on time can be delayed.
Not available for the IP models
Time delay after disconnecting the application for a re-
newed activation of the upstream supply. If the upstream
supply returns while or afterwards the shutdown process,
the application will be restarted via the output voltage of
the UPS.
51