DIP switch 4:
On: Short press is daylightindependent
Off: Short press is daylight-dependent.
NB: Long push is always daylight-independent.
NB: If ECO Off is used, the detector will be blocked for 10 sec. to
prevent momentary re-activation (switching the light on).
Setting sensitivity: Fig. 6.
Setting via potentiometers: Fig. 7.
Lux:
The potentiometers for setting the light level have 10 preset
settings: 20/50/100/200/300/400/500/700/1000 lux and ∞
(daylight-independent).
Example:
The potentiometer is set at 300 lux and the setting can be
increased to 400 lux. When the LUX potentiometer is carefully
turned to a higher lux, the green LED flashes once. The detector
acknowledges with six flashes from the red LED equivalent to
400 lux.
Time:
The potentiometers for setting time (Time) have eight preset
settings: Test/Pulse/2 min/5 min/10 min/15 min/30 min and 60
min. Pulse is 5 seconds On and 55 seconds off.
Example:
The potentiometer is set at 10 minutes and the setting can
be increased to 15 minutes. When the TIME potentiometer is
carefully turned to a longer duration, the green LED flashes once.
The detector acknowledges with five flashes from the red LED
equivalent to 15 minutes.
In order to achieve a secure setting of the potentiometers, the
LED will flash in acknowledgement of the correct setting with a
red LED. Each time the Lux or Time potentiometers are set, the
green LED flashes once.
Lux
20
50
100 200 300 400 500 700 1000
Num-
ber of
1
2
3
4
flashes
Learn actual lux is only possible via IR remote control type
41-926 (accessory).
Time
2
Pulse
minutes
Number of
1
2
flashes
Test:
A walk-test can be carried out to check that the detector is
detecting correctly. Select the walk-test either via the Time
potentiometer (minimum position) or via the "Test On/Off"
button on the IR remote control 41-926 (accessory).
When the walk-test is activated, the blue LED switches on,
and when the detector detects movement, the red LED and
connected lighting will switch on for five seconds.
NB! The walk-test is daylight-independent.
Servodan A/S | Tel +45 7442 4726 | Fax + 45 7442 4035 | info@servodan.dk | www.servodan.com
5
6
7
8
9
5
10
15
30
minutes
minutes
minutes
minutes
3
4
5
6
Examples
Example 1:
E.g. Warehouse
DIP switch settings:
1
2
On
x
Off
Automatic on/off via detector, daylight-dependent. Light sensor
has first priority.
The light switches on automatically when the detector registers
activity within the coverage range and the light level is below the
preset level.
The light switches off automatically after a predetermined period
when registration of activity in the detector's coverage area has
ceased, or the light level remains above the preset level for five
minutes.
The light can always be switched on via the operating button.
Short press.
Setting the light level and cut-off time is performed via the
integrated potentiometers or via the IR remote control 41-926
(accessory).
Option for manual off (ECO off). Short press.
230 V operating button must be connected.
It is possible to perform a long press via the operating button.
A long press is intended for situations in which the light needs
to be switched on (e.g. stocktaking) or switched off (e.g. energy
optimisation) for extended periods.
If the light is on, the light will switch off and the detector will be
disabled as long as activity is detected and the cut-out time + 2
∞ learn
hours has not elapsed. Then the detector switches to automatic
and the light will be switched on in accordance with the selected
application.
10
11
For example: The time has been set to 15 minutes, so the
detector will switch to automatic mode 2 hours and 15 minutes
after it last detected activity.
If the light is off and a long press is activated, it will turn on
60
(regardless of the light level), and the detector keeps it turned
minutes
on as long as activity is detected and the cut-off time + 2 hours
has not run out. The light then turns off, the detector switches
7
to automatic mode, and the light switches on according to the
selected application.
When a long press is activated, the detector indicates this by
flashing the red LED (0.25 seconds On and 5 seconds Off).
If the "long press" function must be interrupted, this is done via a
"short press", after which the detector returns to automatic and
the light switches on according to the selected application.
Example 2:
E.g. offices, double height premises
DIP switch settings:
1
2
On
Off
x
3
4
x
x
3
4
x
x