TECHNICAL SPECIFICATION
System Compatibility:
Environment:
Operating Temperature: -25 to +70
Storage Temperature:
Operating Humidity:
Dimensions:
Height
(including mounting flange):
Diameter:
Weight:
Mounting Requirements: Flat surface or suitable electrical
Electrical Characteristics:
Standby:
Alarm:
! CAUTION: ENSURE THAT SITE PLAN DEFINES THE
POLARITY OF POLARITY CONSCIOUS BASES.
Electromagnetic Compatibility
The FC430SB complies with the following:
Ø product family standard EN50130-4 in respect of Conducted
Disturbances, Radiated Immunity, Electrostatic Discharge,
Fast Transients and Slow High Energy;
Ø EN61000-6-3 for emissions.
INTRODUCTION
The FC430SB Loop Low Power Sounder Base provides an addi-
tional sounder function on the FC addressable loop circuit. The
FC430SB Loop Low Sounder Base requires an associated detec-
tor in order to operate, as it uses the address of the detector that is
fitted to it. Removal of the detector or loss of power to the loop will
cause the sounder to cease operating. A maximum of 45 Sounder
Bases at full volume may be connected to the loop.
FIG. 1
Loop Low Power Sounder Base
use only with FC Fire Alarm Controllers
Indoor Application only
o
C
o
-40 to +80
C
Up to 95% non-condensing
37.5 mm
110 mm
0.186 Kg
backbox with 50 to 70 mm fixing cen-
tres with the 4" flange.
200 mA typical
6.8 mA at full volume (90 dBA)
1.2 mA at low volume (68 dBA)
ENGLISH
FEATURES
The FC430SB provides eight tone and variable volume settings.
WIRING NOTES
The following notes apply.
1) All wiring must conform to the applicable standards.
2) All wiring must be free of earths.
SETTING SOUNDER OUTPUT OPTIONS
The sounder outputs are set as follows:
Ø Tone – using the 4-way DIL switch (Fig. 3 and Table 1 refer).
Ø Volume – using the trimmer tool (FC490VA) (Fig. 3 refers).
Dutch
Temporal 4*
Slow Sweep*
March Time Beep*
Fast Sweep
Temporal 3
Two Tone*
Continuos*
TAB. 1 *) These tones are not LPCB approved
INSTALLATION TO A FLAT SURFACE OR ELECTRICAL
BACKBOX
To install a sounder base, proceed as follows.
1) Feed the addressable loop wiring through the mounting flange
cable entry.
2) Secure the mounting flange to either an electrical backbox or a
flat surface as required.
3) Feed the addressable loop wiring through the sounder base
cable entry, then clip the sounder base to the mounting flange.
DIL SWITCHS SETTINGS
RESPONSE SOUND
Marketing Tone No.