EASYZONE ASSEMBLY

EN
Important: It is recommended to insulate all the metal parts of Easyzone that are exposed to outdoor conditions in order to
prevent condensation.
FR
Remember: The motorized elements are numbered the following way:
IT
Plenums from 2 to 6 dampers
PT
DE

ASSEMBLY TO INDOOR UNIT

Locate the fixing holes. If they are covered, use a screwdriver to uncover them in order to assemble the Easyzone in the
unit.
Important: If your unit has circular adapters in the front part, remove it and mount the adapter to Easyzone provided by Airzone.
Place the Easyzone in the pressure port of the unit and attach it to this using the screws.
After fixing screws be sure to insulate the connection frame to prevent condensation forming. Use bands of insulating
material (glass wool or polyethylene foam) of a thickness of 25 mm. The width of the insulation bands are 97 mm for Standard
and Medium motorized plenum and 36 mm for Slim motorized plenum.
Attach the Easyzone to the ceiling through the tabs on the ends with threaded rods.
22
certificates, watch our videos and read our declaration of conformity at:
myzone.airzone.es/productos/
Plenums of 7 and 8 dampers