Herunterladen Inhalt Inhalt Diese Seite drucken

Technical Data - S+S Regeltechnik Aerasgard Rlq-Co2 Bedienungs- Und Montageanleitung

Inhaltsverzeichnis
Verfügbare Sprachen

Verfügbare Sprachen

G
®
AERASGARD
  RLQ - CO
The self-calibrating microprocessor-controlled AERASGARD
detect the air quality regarding VOC and the CO
made of plastic, with snap-on lid, base with 4-hole attachment for installation on
vertically or horizontally installed in-wall flush boxes, with predetermined breaking
point for on-wall cable entry. or in enclosures made of stainless steel (top and
bottom part are of stainless steel, the lid is screwed on), vandalism-secure version
e.g. for schools, military barracks, and public buildings. The CO
determined by a NDIR sensor (non-dispersive infrared technology). The detection
ranges of these sensors are calibrated for standard applications such as monitoring
of residential rooms or conference rooms. Room venti lation on an as-needed basis,
improvement of well-being and customer benefit, increased comfort as well as a
reduction of operating costs by energy conservation are only some of the beneficial
results of employing AERASGARD
alternative to choose between three sensi bility ranges for VOC monitoring by means
of jumpers, comparable to three measuring ranges: LOW for low, MEDIUM (default,
equivalent to the hitherto existing type of this device) for medium, and HIGH for high
VOC sensibility.Also three measuring ranges were introduced for CO
urement. The selection between the measuring ranges 0...2000 ppm (default, equiv-
alent to the hitherto existing type of this device), 0...5000 ppm, and 0...10000 ppm is
likewise enabled via jumpers.
TECHNICAL DATA:
Power supply: .................................. 24 V AC ⁄ DC
AIR QUALITY  (VOC)
Air quality sensor: .......................... VOC sensor (metal oxide)
Measuring range: ........................... 0...100 % air quality referred to calibrating gas,
Output, air quality: ......................... 0 - 10 V (0 V = clean air, 10 V = polluted air)
Measuring accuracy, VOC: ........... ± 20 % of final value (referred to calibrating gas)
Service life: ...................................... > 60 months (under normal load conditions)
CARBON DIOXIDE  (CO
)
2
CO
sensor: ..................................... optical sensor (NDIR),
2
Measuring range, CO
: ................. multi-range switching  (selectable via jumper)
2
Output CO
: ..................................... 0 - 10 V or with
2
Measuring accuracy, CO
: ............ ± 100 ppm
2
Pressure dependence: .................. ± 1.6 % ⁄ kPa (referred to standard pressure)
Long-term stability: ....................... ± 1 % of final value per year
Service life: ...................................... > 12 years
Gas exchange: ................................. by diffusion
Electrical connection: .................... 0.14 - 1.5 mm
Enclosure: ........................................ plastic, material ABS,
Dimensions: ..................................... 98 x 106 x 32 mm (Frija II)
Installation: ...................................... wall mounting or on in-wall flush box, Ø 55 mm,
Protection class: ............................ III (according to EN 60 730)
Protection type: ............................. IP 30 (according to EN 60 529)
Standards: ....................................... CE-conformity,
Optional: ........................................... 8-digit display, cutout 36 x14 mm (W x H),
2
®
content in air. Elegant enclosure
2
®
RLQ-CO
sensors. The new design implies the
2
(VOC = volatile organic compounds)
multi-range switching (selectable via jumpers)
VOC sensibility: LOW – MEDIUM – HIGH
or with potential-free changeover contact (24 V)
non-dispersive infrared technology
0 ... 2000  ppm;  0 ... 5000  ppm;  0 ... 10000  ppm
potential-free changeover contact (24 V)
2
, via terminals on circuit board
colour pure white (similar RAL 9010),
stainless steel enclosure optional
100 x 100 x 25 mm (stainless steel enclosure)
base with 4-hole for mounting on vertically or
horizontally installed in-wall flush boxes for cable
entry from the back, with predetermined breaking
point for on-wall cable entry from top ⁄ bottom in
case of plain on-wall installation
electromagnetic compatibility
according to EN 61 326 + A1 + A2,
EMC directive 2004 ⁄ 108 ⁄ EC,
low-voltage directive 73 ⁄ 23 ⁄ EEC
for displaying actual air quality (VOC)
and actual CO
content
2
RLQ-CO
is used to
2
Connecting diagram 
content in air is
2
Connecting diagram 
content meas-
2
Schematic diagram
manu/auto
1
UB- GND
2
UB+ supply voltage 24V AC/DC
3
Output 0-10V CO
-content n ppm
2
4
Output 0-10V air quality (VOC)
UB- GND
1
UB+ supply voltage 24V AC/DC
2
3
Output 0-10V CO
-content n ppm
2
4
Output 0-10V air quality (VOC)
5
Normally open
contact
6
Breaker
7
CO
probe
2
CO
/ VOC
2
Function switch
min. max.
(RLQ-CO
-W)
2
7
6
5
4
3
set CO
2
CO
range
2
RLQ - CO
2
RLQ - CO
- W
2 
RLQ - CO
2
RLQ - CO
- W
2 
2
1
manu/auto
set VOC
VOC sensibility
Inhaltsverzeichnis
loading

Inhaltsverzeichnis