The room motion and light sensor KINASGARD
that detects motion and light intensity using a diffuser as well as the presence of
persons and is used to recognize conditions. RBWF-LF issues a standard signal of
0 - 10 V or 4...20 mA for light intensity and has a switching (normally open contact)
output for detecting motion. This multi-sensor is used in building automation,
in corridors, at workplaces, in industrial halls, in offices and business facilities for the
control of lighting as needed, e.g. to control sunshade equipment, for daylight-
dependant constant light control, for activating Venetian blinds or luminaries,
for automatic energy conservation, and to avoid unnecessary heating-up or cooling
of unoccupied rooms.

TECHNICAL DATA

Power supply:
for U variant: 24 V AC (± 20 %); 15...36 V DC (± 10 %)
for I variant: 15...36 V DC (± 10 %) depending on
working resistance, stabilized, max ripple 0.5 Vss
Power consumption:
< 1 W at 24 V DC; < 2 VA at 24 V AC
Sensor:
infra-red motion sensor
and light sensor with diffuser
Output, motion sensor:
without ⁄ with motion + presence,
potential-free normally open contact 24 V / 1A
After-running time:
adjustable from 4 s to 16 min
Measuring ranges:
multi-range switching (via DIP switches)
with 4 switchable measuring ranges
0...500 Lux ⁄ 1 kLux ⁄ 5 kLux ⁄ 20 kLux
(other individual ranges optional, e. g. 100 kLux)
Output, light sensor:
0 -10 V (linearised, active, 3-wire connection) or
4...20 mA
Measuring error:
< 5 % of final value
Ambient temperature:
0...+50 °C
Electrical connection:
0.14 - 1.5 mm², via terminal screws on circuit board
Enclosure:
plastic, material ABS,
colour pure white (similar to RAL 9010)
Dimensions:
85 x 85 x 27 mm (Baldur 1)
Installation:
wall mounting or on in-wall flush box, Ø 55 mm,
base with 4-hole for mounting on vertically or
horizontally installed in-wall flush boxes for cable entry
from the back, with predetermined breaking point
for on-wall cable entry from top ⁄ bottom
in case of plain on-wall installation
Protection class:
III (according to EN 60 730)
Protection type:
IP 20 (according to EN 60 529)
Standards:
CE conformity, electromagnetic compatibility
according to EN 61 326, EMC directive 2004 ⁄ 108 ⁄ EC
Type ⁄ WG01
Detection, Measuring Range
RBWF ⁄ LF
Room motion sensor and light sensor
Presence + Motion : Yes ⁄ No (relay on ⁄ off)
R B W F - L F - U
Light Intensity: 0...500 Lux ⁄ 1 kLux ⁄ 5 kLux ⁄ 20 kLux
Presence + Motion : Yes ⁄ No (relay on ⁄ off)
R B W F - L F - I
Light Intensity: 0...500 Lux ⁄ 1 kLux ⁄ 5 kLux ⁄ 20 kLux
RBWF
Room motion sensor
R B W F -W
Presence + Motion : Yes ⁄ No (relay on ⁄ off)
RHKF
Room light intensity sensors
R H K F - I
Light Intensity: 0...500 Lux ⁄ 1 kLux ⁄ 5 kLux ⁄ 20 kLux
R H K F - U
Light Intensity: 0...500 Lux ⁄ 1 kLux ⁄ 5 kLux ⁄ 20 kLux
®
RBWF-LF is a combined instrument
Schematic diagram
UB+ 24V AC/DC
Output Light
Intensity in lux
UB- GND
Presence
detector
13 11 12
Connecting diagram
UB+ supply voltage 24V AC/DC
1
2
Output light intensity 0-10V (linearised)
3
UB- GND
13
Normally
open contact
11
12
Breaker
Measuring ranges
selectable
0...500 Lux
0... 1 kLux
0... 5 kLux
0... 20 kLux
Output
Changeover contact
0 - 10 V
(linearised)
Changeover contact
4 ... 20 mA
Changeover contact
4 ... 20 mA (linearised)
0 - 10 V
(linearised)
Rev. 2016 - V20 GB
RBWF ⁄ LF
ON
1 2 3 4
1
2
3
offset time
4'' 16'
RBWF ⁄ LF
changeover
(24 V)
DIP
DIP
DIP
DIP
1
2
3
4
O N
OFF
OFF
OFF
OFF
O N
OFF
OFF
OFF
OFF
O N
OFF
O N
OFF
OFF
OFF
Item No.
1401-41A 1-1100 -000
1401-41A 1-3200 -000
1401-41A 0-4000 -000
1601-41A 2-2000 -000
1601-41A 1-2000 -000

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis