INSTALLATION
ZERO POINT ADJUSTMENT (potentiometer P4)
Example 1: At a setpoint of 1 volt, the output pressure should be 3 bar: Apply a setpoint of 1 volt and turn potentiometer P4 clockwise
until 3 bar are reached.
Example 2: At a setpoint of 2 volts, the output pressure should be 0 bar: Apply a setpoint of 2 volts and turn potentiometer P4
counterclockwise u n t i l 0 b a r i s o b t a i n e d .
Turn
potentiometer P4
clockwise
Max. output
pressure
0
2 V
In order to avoid damaging the pressure sensor, the supply pressure must always be less than the maximum input pressure
defined above.
SPAN ADJUSTMENT (potentiometer P3)
Example for a valve adjustment with a maximum output pressure of 6 bar.
At a setpoint of 0 - 10 Volts the output pressure should be 0 to 5 bar:
Apply a setpoint of 10 Volts and turn potentiometer P3 counterclockwise until 5 bar are reached at the valve output.
Max.
output pressure
Max. output
pressure
0.75
0
The span can be adjusted between 75 and 100 % of the maximum output pressure.
The factory setting is 100 %.
5 V
10 mA
Span adjustment with
potentiometer P3
Saturation zone
Turn potentiometer P4
counterclockwise
10 V
20 mA
Turn potentiometer clockwise.
Turn potentiometer counterclockwise.
10 V
20 mA
PULSTRONIC
Input pressure
Max. output
pressure
MIN.
( b a r )
( b a r )
1 (
)
1 , 5
*
2
2 , 5
3
3 , 5
6
6 , 5
10
10,5
(
) Only on DN 0.5
*
MAX.
( b a r )
2
5
5
8
12
7