Herunterladen Inhalt Inhalt Diese Seite drucken

Scope Of Delivery; Determined Use; Specifications; Permitted Maximum Values - Bosch BH 500-6 B Installations- Und Wartungsanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
2.2

Scope of delivery

500 litre cylinder
• Storage cylinder made of PU rigid foam
• Thermal insulation:
– ErP "B": additional thermal insulation, 40 mm
– ErP "C": foil jacket on flexible foam underlayer
• Casing lid
• Upper insulation
• Technical documents
750...1300 litre cylinder
• Storage cylinder
• PU rigid foam halves
• Thermal insulation:
– ErP "B": polystyrene jacket, packaged separately
– ErP "C": foil jacket on flexible foam underlayer
• Casing lid
• Upper insulation
• Floor insulation
• Bag of small parts
– Fleece strip
– Fleece circular blank
– Compass and plug
• Technical documents
2.3

Determined use

These buffer cylinders may only be filled with heating water and used in
sealed heating systems.
The buffer cylinders can be used for indirect potable water heating via a
freshwater station.
Only fill solar heat exchangers with propylene glycol/water mixtures
(heat transfer medium L or LS). The use of any other heat transfer
medium is not permitted.
BH/B/B...M/B...ER/BS...ER/BH...ERZ/BHS...ERZ
2.4

Specifications

• Technical data ( Fig. 1, page 58 and Fig. 2, page 59).
• Pressure drop diagram for solar heat exchanger ( Fig. 3, page 60).
2.4.1

Permitted maximum values

Unit
Operating pressure for the
bar
water
Operating pressure
bar
solar heat exchanger
Operating temperature
heating water
Operating temperature
solar heat exchanger
Maximum recommended flow
m
rate through connector 1 1/2"
Temperature-dependent feed
m
flow rate:
3
Maximum 5 m
/h, function
successfully tested up to:
Table 3 Permitted maximum values
2.4.2

Data plate

The data plate is located on the left, next to the connections
( Fig. 14, [2], page 64).
Position Description
1
Model designation
2
Serial number
3
Actual capacity
6
Year of manufacture
9
Maximum flow temperature, heat source
10
Maximum flow temperature, solar
17
Maximum operating pressure, heat source side
18
Maximum operating pressure, solar side
Table 4 Information on the data plate
Product information | 39
BH...
B...
BS...ER
B...
BH...
BHS...
B...M
ERZ
ERZ
3
3
3
10
°C
95
95
95
°C
130
3
/h
approx.
approx.
approx.
5
5
5
3
/h
1.5
1.5
6 720 817 513 (2017/08)
BH...
PN6
6
95
approx.
5

Werbung