G
®
HYGRASGARD
Function 05 Write Single Coil
Register
0x0001
Reset (Auto zero) CO2
0x0002
Reset (Auto zero) VOC
0x0003
Automatic calibration (Automatic) CO2
0x0004
Automatic calibration (Automatic) VOC
0x0005
VOC sensibility "low"
0x0006
VOC sensibility "medium"
0x0007
VOC sensibility "high"
Function 08 Diagnostics
The following sub function codes are supported
Sub Function
Parameter
Code
00
Echo of transmission data
(Loopback)
01
Restart Modbus
(Reset listen-only mode)
04
Activation listen-only mode
10
Delete counter
11
Counter bus telegrams
12
Counter communication errors
(Parity, CRC, frame errors, etc.)
13
Counter exception telegrams
14
Counter slave telegrams
15
Counter telegrams without answer
Function 17 Report Slave ID
Composition of answer telegram
Byte No.
Parameter
00
Number of bytes
01
Slave ID (device type)
02
Slave ID (device class)
03
Status
04
Version number (release)
05
Version number (version)
06
Version number (index)
AFTM- ⁄ KFTM - LQ - CO
Parameter
- Modbus | Telegrams
2
Data Type
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Data Type
Unsigned 16 bit
Unsigned 16 bit
Unsigned 16 bit
Unsigned 16 bit
Unsigned 16 bit
Data Type
Unsigned 8 bit
Unsigned 8 bit
Unsigned 8 bit
Unsigned 8 bit
Unsigned 8 bit
Unsigned 8 bit
Unsigned 8 bit
22
Value
Range
0 / 1
OFF - ON
0 / 1
OFF - ON
0 / 1
OFF - ON
0 / 1
OFF - ON
0 / 1
OFF - ON
0 / 1
OFF - ON
0 / 1
OFF - ON
Answer
Echo data
Echo telegram
No answer
Echo telegram
All valid bus telegrams
Faulty bus telegrams
Error counter
Slave telegrams
Broadcast messages (address 0)
Answer
6
®
14 = AERSGARD
MODBUS
®
60 = AERASGARD
/ AERASREG
255 = RUN, 0 = STOP
1...9
1...99
1
®