S+S REGELTECHNIK AERASGARD KFTM-LQ-CO2 Modbus Bedienungs- Und Montageanleitung Seite 21

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

  • DEUTSCH, seite 3
G
®
HYGRASGARD
TELEGRAMS
Function 04 Read Input Register
Register
3x0001
CO2
3x0002
CO2
3x0003
VOC
3x0004
VOC
3x0005
Temperature
3x0006
Temperature
3x0007
Relative humidity
3x0008
Relative humidity
3x0009
Atmospheric pressure
3x0010
Atmospheric pressure
Function 06 Write Single Register & Function 16 Write Multiple Register
Register
4x0001
Physical parameter displayed
Standard display (cyclic):
VOC in %,
CO2 in ppm,
temperature in °C,
relative humidity in % r.H.
alternative display (static):
CO2 in ppm
VOC in %
Temperature in °C
Relative humidity in % r.H.
Atmospheric pressure in hPa
Freely configurable display
4x0002
7-Segment Value
4x0003
7-Segment Value
4x0004
4x0005
Segment Pattern
4x0006
Dot Matrix Character A
4x0007
Dot Matrix Character B
4x0008
Dot Matrix Character C
4x0009
Dot Matrix Character D
4x0010
Dot Matrix Character E
4x0011
Dot Matrix Character F
4x0012
Dot Matrix Character G
4x0013
Dot Matrix Character H
4x0014
Dot Matrix Character I
4x0015
Dot Matrix Character J
4x0016
Dot Matrix Character K
4x0017
Dot Matrix Character L
4x0018
Dot Matrix Character M
4x0019
Dot Matrix Character N
AFTM- ⁄ KFTM - LQ - CO
Parameter
Sampling 4 s
Filtering 32 s
Sampling 4 s
Filtering 32 s
Sampling 4 s
Filtering 32 s
Sampling 4 s
Filtering 32 s
Sampling 4 s
Filtering 32 s
Parameter (display)
- Modbus | Telegrams
2
Data Type
Signed 16 bit
Signed 16 bit
Signed 16 bit
Signed 16 bit
Signed 16 bit
Signed 16 bit
Signed 16 bit
Signed 16 bit
Signed 16 bit
Signed 16 bit
Data Type
Index on display
Unsigned 8 bit
1
2
3
4
5
Signed 16 bit
Signed 8 bit
Unsigned 16 bit
Unsigned 8 bit
Unsigned 8 bit
Unsigned 8 bit
Unsigned 8 bit
Unsigned 8 bit
Unsigned 8 bit
Unsigned 8 bit
Unsigned 8 bit
Unsigned 8 bit
Unsigned 8 bit
Unsigned 8 bit
Unsigned 8 bit
Unsigned 8 bit
Unsigned 8 bit
21
Value
Range
350...5000
350...5000 ppm
350...5000
350...5000 ppm
0...1000
0.0...100.0 % VOC
0...1000
0.0...100.0 % VOC
–350...800
–35.0...+80.0 °C
–350...800
–35.0...+80.0 °C
0...1000
0.0...100.0 % r.H.
0...1000
0.0...100.0 % r.H.
700...1100
700...1110 hPa
700...1100
700...1110 hPa
Value
Range
0...10
0...10
Default
0
setting
1
2
3
4
5
10
-999...9999
-999...9999
-9...99
-9...99
See Binary Pattern
0...255
ASCII character
0...255
ASCII character
0...255
ASCII character
0...255
ASCII character
0...255
ASCII character
0...255
ASCII character
0...255
ASCII character
0...255
ASCII character
0...255
ASCII character
0...255
ASCII character
0...255
ASCII character
0...255
ASCII character
0...255
ASCII character
0...255
ASCII character