For the Installer

General
UKV 500 has several different areas of use.
UKV 500 can be used during external control of the
heating system. The heat pump then charges UKV 500
with floating or fixed condensing. The external control
function controls the heat distribution from UKV 500 to
the consumer. If the flow to the heating system can be
restricted using radiator thermostats for example, install
a UKV 500 as an intermediate tank. This ensures a secure
flow for the heat pump. UKV 500 also allows a greater
flow to the heating system than across the heat pump.
In some installations, so-called heat spikes occur as a
result of movements during temperature changes. To
eliminate temporary temperature changes, and thereby
prevent heat spikes, install a UKV 500 after the heating
installation. UKV 500 can also be used to increase the
system volume and prevent malfunctions.
The accumulator tank consists of a steel vessel.
The accumulator tank is designed and manufactured for
a maximum cut-off pressure of 6 bar.
Maximum permitted temperature is 85 °C.
The insulation on the sides of UKV 500 consists of EPS
with a thickness of 85 mm, which provides excellent heat
insulation. The insulation and white plastic outer clad-
ding can easily be removed to make it easier to move
the accumulator tank through doorways, for example.
Transport
UKV 500 should be transported and stored vertically in
a dry place. The UKV 500 may, however, be carefully laid
on its back when being moved into a building.
Assembly
The accumulator tank may only be installed vertically.
The accumulator tank is unscrewed from the pallet and
lifted into position.
Position UKV 500 on a firm base that can take the weight,
preferably on a concrete floor or foundation. Use the
product's adjustable feet to obtain a horizontal and
stable set-up.
The area where UKV 500 is located must be equipped
with floor drainage.
UKV 500 | GB
0
R
0-15 mm
19