Herunterladen Inhalt Inhalt Diese Seite drucken

Wiring Example; Coding; Standard; Individual - Wenglor SD4RAS01SN89 Betriebsanleitung

Sicherheitsschalter
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

EN

6.1.4. Wiring example

• The voltage is supplied at both safety inputs of the terminal sensor chain (considered from the safety­
monitoring module).
• The safety outputs of the first safety switch are wired to the safety­monitoring module. The signal output
can be connected for instance to a PLC.
SD4RAA0x
SD4RAS0xxN89
5
2
6
1
3
24 VDC
GND
OSSD1 and OSSD2 = Safety Outputs => Safety monitoring module

6.2. Coding

6.2.1. Standard

• Safety switches with standard coding (SD4RAS01SN89, SD4RAS02SN89) are ready to use upon delivery.

6.2.2. Individual

• Individually encoded safety switches (SD4RAS01IN89, SD4RAS02IN89, SD4RAS01TN89, SD4RAS02TN89)
are taught according to the following sequence:
1. Energise the safety switch.
2. Introduce the actuator in the detection range. The teach­in procedure is signalled at the safety switch red
LED on, yellow LED flashes (1 Hz).
3. After 10 seconds, brief cyclic flashes (3 Hz) request the switch­off of the operating voltage of the safety
switch. (If the voltage is not switched off within 5 minutes, the safety switch cancels the "teach­in" procedure
and signals a false actuator by 5 red flashes).
4. After the operating voltage is switched back on, the actuator must be detected once more in order to activate
the taught actuator code. In this way, the activated code is definitively saved!
• For ordering SD4RAS01IN89 and SD4RAS02IN89, the thus executed allocation of safety sensor and
actuator is irreversible.
34
7
4
8
OSSD1
OSSD2
SD4RAA0x
SD4RAS0xxN89
5
2
6
1
3
7
4
OSSD1
IN1
IN2
OSSD2
8
Initial Start­Up

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis