Herunterladen Diese Seite drucken

SOMFY 1860116 Gebrauchsanweisung Seite 10

Knx 4 ac motor controller wm/drm
Vorschau ausblenden Andere Handbücher für 1860116:

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
GB
A
PICTURES
[1] 4 AC Motor Controller WM 220-230 V AC,
wall mounted version
[2] 4 AC Motor Controller DRM 220-230 V AC,
DIN rail mounted version
B
MOUNTING
[1] Choose the optimal location: flat and large surface
[2] Mount the 4 AC Motor Controller WM
[3] DIN Rail mounted version
1.
Electrical cabinet
[4] Use cable tie!
[5] Connect power supply and wiring to the
Motor Controller
C
WIRING
[1] Tool for all terminals
[2] Wiring diagram
[3] Check the correct running directions of the end product
UP: the end product goes up ( C + s)
STOP: the end product stops ( C + t+ s)
DOWN: the end product goes down ( C + t)
To close window press UP, to open window press
DOWN.
[4] Possible switches
1.
Smoove Origin IB, Ref. 1811272
2.
Double push button
D
CONFIGURATION
[1] Reset / Prog button
With this button, you can access the basic configura-
tion of the Motor Controller.
The „US" LED is steadily blinking when the mains (230 V)
and the KNX bus power are actively connected to the
device. The device is ready for operation when the „US"
LED is blinking. The Reset / Prog button can be used to
select a switch ergonomic when the device is in default
condition and is not programmed by the ETS Software.
The different ergonomics are described in the user manual.
CABLE
Connection to ...
Motors
Switches
Group control
KNX bus
220 - 230 V AC
Cables
Min.: 4 x 0.75 mm
/19 AWG
2
Max.: 4 x 2.5 mm
/14 AWG
2
Min.: 3 x 0.6 mm/22 AWG
Max.: 3 x 2.5 mm
/14 AWG
2
Min.: 3 x 0.6 mm/22 AWG
Max.: 3 x 1.5 mm
/16 AWG
2
2 x 0.8 mm/20 AWG
Min.: 3 x 1.5 mm
/16 AWG
2
Max.: 3 x 2.5 mm
/14 AWG
2
[2] Selection of switch ergonomic
Local push button ergonomics and the type of end
products to be preselected:
• Screen mode
• Venetian blind, European mode
• Venetian blind, US mode
The default mode is: Venetian blind, EU mode.
1.
To toggle between modes, press shortly the
Reset / Prog button. Repeat until the LED,
according to the desired configuration, lights up.
[3] Factory RESET
[4] Learn running and tilting times/length
1.
Press immediately when lower end limit
is reached
2.
Maintain stop for duration of tilting
[5] Symbols: actions
1.
Up
2.
Stop
[6] Symbols: end product status
1.
Up
2.
High position
3.
Down
4.
Low position
When electronic motors are to be controlled through this
Motor Controller device it is mandatory to configure the start-
up delay time for electronic motors in the Motor Controller
settings. To configure the start-up delay time WT Setting Tool
Ref. 1811242 can be used.
Twisted pairs
-
Recommended
Recommended
Required, following KNX
topology guidelines
-
animeo KNX 4 AC MOTOR CONTROLLER . REF. 5062283E -
Max. distance
150 m
100 m
50 m
10/16

Werbung

loading

Diese Anleitung auch für:

1860114