Intended Use

The ProLine P 44000 Pt100 transmitters isolate and convert the signal
of a Pt100 resistive sensor into a 4 to 20 mA current signal. They are
designed specifically for applications with high working voltages
which require high insulation strength to protect parts of the installa-
tion and where the insulation of the resistive sensor is not sufficient.
The devices have a broad-range power supply 22 ... 230 V AC/DC
± 10 % and galvanic 3-port isolation.

Block Diagram

Input
WARNING!
For applications with high working voltages, take measures
to prevent accidental contact and make sure that there is
sufficient distance or insulation between adjacent devices.
26
Power supply: 22 ... 230 V AC/DC ± 10 %
+
C
Z 15 V
Output
1 nF