Herunterladen Inhalt Inhalt Diese Seite drucken

Technical Specification - Bosch RML 0008 A Montageanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 7
English
Functional description
The relay low voltage module provides 8 dry contact form C relay outputs, to switch external
loads. Each output has a normally opened (NO) and normally closed (NC) contact option.
Wiring
Pos.
Marking
1
NO1
2
C1
3
NC1
4
NO2
5
C2
6
NC2
7
NO3
8
C3
9
NC3
10
NO4
11
C4
12
NC4
13
NO5
14
C5
15
NC5
16
NO6
17
C6
18
NC6
19
NO7
20
C7
21
NC7
22
NO8
23
C8
24
NC8

Technical Specification

Input voltage (min − max)
Max. current consumption
− standby mode
− all relays actuated
Max. relay contact rating
Safety class
EMI / EMC protection
Protection class
Operating Temperature
Storage Temperature
Permissible relative humidity
Housing material and color
Dimensions (H x W x D)
Weight
Product description RML 0008 A
Connection
Relay Output 1
Relay Output 1
Relay Output 2
Relay Output 2
Relay Output 3
Relay Output 3
Relay Output 4
Relay Output 4
Relay Output 5
Relay Output 5
Relay Output 6
Relay Output 6
Relay Output 7
Relay Output 7
Relay Output 8
Relay Output 8
20 V DC − 30 V DC / 5 V DC $5%
3.3 mA
85.8 mA
30 V DC / 1 A
II as per IEC 60950 / EN 60950
EN 50081−1 / FCC Part 15
IP 30 as per IEC 60529
−5 _C . . . 50 _C
−20 _C . . . 60 _C
max. 95% non condensing
ABS plastic Polylac PA−766 (UL94 V−0),
semi gloss anthracite, RAL 7016
approx. 127 x 96 x 60 mm (5.0 x 3.8 x 2.4 inches)
approx. 150 g (5.3 ounces)
13 / 32
1 2
3 4 5 6 7 8 9 10 11 12
13 14 15 16 17 18 19 20 21 22 23 24
(23 _F . . . 122 _F)
(−4 _F . . . 140 _F)
4.998.137.265
610−4.998.153.973 / A2
ST − FIR / PRM1 / deh