5.4/ Tubes Collectors:
GB
Select the lines "Tubes collectors" and press
- Now select with
(Vacuum tubes collector).
- This function could be used if the collector sensor is not directly mounted on
the collector. This function works in the following way.
Each 30 minutes the pump will be activated 30 seconds to measure the
correct value on the collector to avoid short charge cycle.
5.5/ Protection func. :
- Once the line selected press
5.5.1/ Max temp:
- Setting level to start the overheat protection for the collector array.
(Adjustable 110 to 150°C with factory value 120°C)
The overheat collector protection is alaways active.
This function active the pump circulation when the collector temperature is
above "Maxtemp" plus 10°C
(The pumps will be stopped when the water temperature in the tank will reach
95°C).
---------------
Service---
English
System
Extra
off
Tubes collectors
Protection func.
Flow meter
Flow (l/min)
or
"yes" if you want to use this type of collectors
---------------
Service---
English
System
Extra
off
Tubes collectors
Protection func.
Flow meter
Flow (l/min)
to enter the submenu.
Protection
func.---
Collector
Max temp
Cooling
Freeze prot
16
- --- --
no------
no
10
to highlight the line.
- --- --
no
no
---------------
120°C
no
no