Modification and installation

6.1

Installation instructions

In addition to the general rules of DIN VDE 0100 - "erection of low-voltage systems", various standards and
regulations must be complied with. DIN VDE 18040-1 is the basis for the design and function of a call system.
The special conditions in rooms used for medical purposes and general rules of telecommunications
technology also apply. The ambient conditions must correspond to class 3k3 or 3k4 in accordance with DIN
EN 60721-3-3. To protect against dangerous shock currents, the respectively required protective measures
must be employed in rooms of application groups 1 and 2.
It may be necessary to follow additional regulations during the course of setting up the system, depending on
the installation or location.
In WCs and wet rooms, the special provisions of DIN VDE 0100 must be observed. Only correspondingly
suitable devices may be installed in these rooms. Observe the instructions of the manufacturer that specially
designate the devices as suitable for installation in WCs and wet room areas.
Pull switches, etc. in showers must be installed at least 20 cm above the highest possible position of the
shower head, and the pull cord should not be farther than 20 cm away from the top edge of the floor to ensure
that people lying on the floor can still reach the pull cord.
In its standard design, the compact call set is intended for use in dry, indoor rooms. The range of applications
of the corresponding components can be extended to damp rooms through use of the IPx4 seal inserts
(Part No. 88160A).
The devices are not suitable for installation in locations at risk to explosion.
In accordance with DIN VDE 0834-1, connecting cables (including cable laying) must be able to
withstand a test voltage of 4 KV. The power supply of the devices can be fed into the same
cable. Alternatively you may use system cables 89734AH / 89734AJ.
Danger – Electric shock!
Assembly and installation work may only be performed while the module is de-energised
(without power).
Personal injuries
During installation work, the affected rooms may only be entered by qualified personnel.
76910XE / 02.2018