USER INSTRUCTIONS
English
Standard Signal Converter
IsoPAQ-641
Read these instructions before using the product and retain for future information.
IsoPAQ-641
► Before Startup
When operating the signal converter, certain parts
of the module can carry dangerous voltage!
Ignoring the warnings can lead to serious injury
and/or cause damage!
The signal converter should only be installed and
put into operation by qualified staff. The staff must
have studied the warnings in these operating
instructions thoroughly.
The signal converter may not be put into operation if
the housing is open.
In
applications
with
high
operating
voltages
sufficient distance and isolation as well as shock
protection must be ensured.
Safe and trouble-free operation of this device can
only be guaranteed if transport, storage and
installation are carried out correctly and operation
an maintenance are carried out with care.
Appropriate safety measures against electrostatic
discharge (ESD) should be taken during range
selection and assembly on the transmitter.
► Short description
The Standard Signal Converter is used for electrical isolation and
conversion of unipolar process signals. The input and output range
can be set by using DIP switch and due to the calibrated range
selection no further adjustment is necessary.
The 3-way isolation guarantees reliable decoupling of the sensor
circuit from the processing circuit and prevents linked measurement
circuits from influencing each other. The Protective Separation with
high isolation level
provides protection for personnel
downstream devices against impermissibly high voltage.
The auxiliary power can be supplied via the connection terminals or
type-specific
via
the
optional
In-Rail-Bus
connector
accessories). A green LED on the front of the unit has been provided
to monitor the power supply.
► Functioning
The input signal is modulated and then electrically decoupled using
a transformer. The isolated signal is then made available at the
output, demodulated, filtered and amplified.
► Settings
Set the input and output ranges with DIP switch as indicated in the
following table:
S1 -
Input
Output
1
2
3
4
0 ... 20 mA
4 ... 20 mA
0 ... 20 mA
0 ... 10 V
2 ... 10 V
0 ... 20 mA
4 ... 20 mA
4 ... 20 mA
0 ... 10 V
2 ... 10 V
0 ... 20 mA
4 ... 20 mA
0 ... 10 V
0 ... 10 V
2 ... 10 V
0 ... 20 mA
4 ... 20 mA
2 ... 10 V
0 ... 10 V
2 ... 10 V
Filter 5kHz
Filter 100 Hz
Filter 10 Hz
Factory settings: all switches in position OFF
► Mounting, Electrical Connection
The isolation transmitter is mounted on standard 35 mm DIN rail.
Terminal assignments
1
Input I +
5
Output +
Input I −
Output −
2
6
3
Input U +
7
Power supply +
Input U −
Power supply −
4
8
► Technical Data
Input
Voltage
Input signal
0 ... 10 V
(calibrated switchable)
2 ... 10 V
≥ 100 kΩ
Input resistance
≤ 30 V
Overload
Output
Voltage
Output signal
0 ... 10 V
(calibrated switchable)
2 ... 10 V
≤ 5 mA (2 kΩ at 10 V)
Load
and
Linear transmission range
-1 to +110 %
Ripple
< 10 mV
rms
General data
Transmission error
< 0.1 % full scale
(see
1)
Temperature coefficient
< 100 ppm/K
Cut-off frequency -3 dB
5 kHz, 100 Hz, 10 Hz
(switchable)
Response time T
150 µs, 7 ms, 70 ms
99
Test voltage
3 kV, 50 Hz, 1 min.
Input against output against power supply
2)
Working voltage
600 V AC/DC for overvoltage category II and
(Basic insulation)
contamination class 2 acc. to EN 61010-1
Protection against
Protective Separation by reinforced insulation acc. to
dangerous body
EN 61010-1 up to 300 V AC/DC for overvoltage
2)
currents
category II and contamination class 2 between input
and output and power supply.
Ambient temperature
Operation
Transport
and storage
Power supply
24 V DC
3)
EMC
EN 61326-1
Construction
6.2 mm (0.244'') housing, protection type: IP 20
5
6
mounting on 35 mm DIN rail acc. to EN 60715
Connection
Solid:
(captive plus-minus
Fine-stranded:
clamp screws)
Stripped length: 6-8 mm / 0.28 in
Screw terminal torque 0.8 Nm / 7 lbf in
Weight
Approx. 70 g
1) Average TC in specified operating temperature range
2) As far as relevant the standards and rules mentioned above are considered
by development and production of our devices. In addition relevant assembly
rules are to be considered by installation of our devices in other equipment.
For applications with high working voltages, take measures to prevent
accidental contact and make sure that there is sufficient distance or insulation
between adjacent situated devices.
3) Minor deviations possible during interference
► Block Diagram
● = on
► Order Information
Product
Input / Output
IsoPAQ-641
calibrated
In-Rail-Bus for power supply
switchable
► Dimensions
Current
0 ... 20 mA
4 ... 20 mA
≤ 25 Ω
≤ 50 mA
Current
0 ... 20 mA
4 ... 20 mA
≤ 12 V (600 Ω at 20 mA)
LIMITED WARRANTY
-25 °C to +70 °C (-13 to +158 °F)
INOR Process AB, or any other affiliated company within the
-40 °C to +85 °C (-40 to +185 °F)
Inor Group (hereinafter jointly referred to as "Inor"), hereby
warrants that the Product will be free from defects in
16.8 V ... 31.2 V, approx. 0.7 W
materials or workmanship for a period of five (5) years from
the date of delivery ("Limited Warranty"). This Limited
Warranty is limited to repair or replacement at Inor's option
and is effective only for the first end-user of the Product. This
2
2
0.5 mm
- 4 mm
/ AWG 20-12
Limited Warranty applies only if the Product:
2
2
0.5 mm
- 2.5 mm
/ AWG 20-14
1.
is installed according to the instructions furnished by
Inor;
2.
is connected to a proper power supply;
3.
is not misused or abused; and
4.
there is no evidence of tampering, mishandling, neglect,
accidental damage, modification or repair without the
approval of Inor or damage done to the Product by
anyoneother than Inor.
Inor specifically disclaims any express warranty not provided
herein and any implied warranty, guarantee or representation
as to suitability for any particular purpose, performance,
quality and absence of any hidden defects, and any remedy
for breach of contract, which but for this provision, might
arise by implication, operation of law, custom of trade or
course
of
dealing,
merchantability and fitness for a particular purpose. Except
as provided herein, Inor further disclaims any responsibility
for losses, expenses, inconveniences, special, direct,
secondary or consequential damages arising from ownership
or
use
Customer pays freight to Inor, and Inor will pay the return
freight by post or other "normal" way of transport. If any other
type of return freight is requested, customer pays the whole
return cost.
INOR Process AB
PO Box 9125
200 39 MALMÖ
Order No.
SWEDEN
Phone:
+46 (0)40 312 560
70ISL64100
Fax:
+46 (0)40 312 570
E-Mail:
support@inor.se
Internet: www.inor.com
including
implied
warranties
of
of
the
product.

Werbung

loading

Inhaltszusammenfassung für INOR IsoPAQ-641

  • Seite 1 Factory settings: all switches in position OFF product. instructions thoroughly. Customer pays freight to Inor, and Inor will pay the return ► Mounting, Electrical Connection The signal converter may not be put into operation if freight by post or other “normal” way of transport. If any other the housing is open.
  • Seite 2 Klemmenbelegung Der Kunde übernimmt die Frachtkosten für den Transport zu hinweisen dieser Betriebsanleitung gründlich INOR, und INOR bezahlt die Rückfracht per Post oder mit Eingang I + Ausgang + auseinandergesetzt haben. Eingang I − Ausgang − anderen ”normalen“ Transportarten. Wenn eine andere Art der Rückfracht verlangt wird, übernimmt der Kunde die...

Diese Anleitung auch für:

70isl64100