Min./Max. adjustment: this is the value of level at "Calibration Lowest Point". The unit is
-
defined in "level_unit"
When writing "cal_level_lo" and "cal_type" = 1, the "Calibration Lowest Point" is automatically set
-
to "sensor_value"
cal_type
l
Min./Max. adjustment: this parameter defines the type of calibration:
-
Dry: no influence of "sensor_value" on level calibration
-
Online: current "sensor_value"determines "Calibration Highest/Lowest Point"
-
level
l
level_unit
l
level_offset
l
sensor_offset
l
end_of_operation_range
l
begin_of_operation_range
l
product_type
l
set up to suit the process conditions
-
liquids_medium_type
l
set up to suit the process conditions
-
solids_medium_type
l
set up to suit the process conditions
-
liquids_vessel_type
l
set up to suit the process conditions
-
solids_vessel_type
l
set up to suit the process conditions
-
fast_level_change
l
set up to suit the process conditions
-
first_echo_factor
l
pulse_velocity_correction
l
echo_quality
l
empty_vessel_curve_corr_dist
l
The actual distance from sensor to the product surface must be entered before creating a
-
false echo memory
The unit is defined in "sensor_range.Units Index"
-
empty_vessel_curve_corr_op_code
l
Create a false echo memory. Selectable codes are: update, create new and delete
-
total_sensor_value
l
VEGAFLEX 63 • Foundation Fieldbus