Heating Mode - Aqua Medic Titan Professional 15.000 Bedienungsanleitung

Vorschau ausblenden Andere Handbücher für Titan Professional 15.000:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

For example: When the water temperature in the aquarium is 25° C and you want to cool it down to
20° C, operate as follows: set temperature is 20° C, compressor and fan will start working after 15
seconds, "Refrigerating" indicator light is on, cooling starts. When the water temperature drops to
20° C, compressor and fan stop working. The "ON" LED lights will be off and the machine stops
cooling.

4.3. Heating Mode

3. When the water temperature in the water tank is lower than the adjusted set temperature -
temperature difference, the compressor and fan will start to work and the heating indicator light
is on. At this time, the machine starts heating.
4. When the water temperature in the water tank has reached the set temperature, compressor and
fan will stop working and the heating indicator light is off. At this time, the machine stops heating.
For example: When the water temperature in the aquarium is 20° C and you want to heat it up to
25° C, operate as follows: set temperature is 25° C, compressor and fan will start working after 15
seconds, "Heating" indicator light is on, heating starts. When the water temperature rises to 25° C,
compressor and fan stop working. The "ON" LED lights will be off and the machine stops heating.
4.4. Fault Code (Titan 6000)
No.
Fault Code
1a
E01
2a
E05
3
E02
4
E03
Fault Code (Titan 8000 - 15000)
No.
Fault Code
1
EE
2a
E1
3a
E2
4
E3
5
E4
6
E5
7
E6
If the flow rate is too low, an error will occur. If it is not possible to increase the water flow, cancel
the water flow meter. Short cut the two black wires (No. 19) at the heat exchanger and the chiller
works without flow control.
Fault Reason
Temperature sensor is open / short-circuit or
exceeds the using range.
Water flow sensor open / short-circuit or out
of using range.
High pressure, pressure fault.
Low pressure, pressure fault.
Fault Reason
Telecommunication lines.
Temperature sensor is open / short-circuit or
out of using range.
Water flow sensor is open / short-circuit or out
of using range.
Titan 8000: high pressure, pressure fault.
Titan 8000: low pressure, pressure fault.
Titan 15000: high pressure, pressure fault.
Titan 15000: low pressure, pressure fault.
Solution
Replace temperature
sensor or adjust the using
range.
Replace water flow switch
or water flow rate is not
enough.
Clean condenser.
Add refrigerant.
Solution
Change telecommunication
lines.
Replace
temperature
sensor or adjust the using
range.
Replace sensor or adjust
the using range.
Clean condenser.
Add refrigerant for No. 1
machine.
Clean condenser.
Add refrigerant for No. 2
machine.
11