SHE control panel TRZ Plus DG
Start up procedure and trial run
Test automatic detectors
Activate automatic detector (e.g. using a test spray), the red LED in the automatic detector illuminates. The red LED
indicating
"SHE activation" illuminates, the green LED
compressed gas generators will be activated. The NSHEVs will open when the compressed gas generators ignite and
the pressure media installed in the NSHEVs (CO
yellow LED fl ashes indicating "OFF". Once the activation has been successfully completed, the slider switch must be
switched to the "secured" position. Press the RESET button on one of the SHE central control units. The red LED
indicating
"SHE activated" goes out at all SHE manual call points and on the main board. The yellow LED indicating
- "malfunction" continues to fl ash (fl ash code 5). The compressed gas generators and the NSHEV energy
sources - CO
/N
bottles - must be replaced and the dome lights must be correctly closed. Remove the smoke from the
2
2
detectors, otherwise they will reactivate!
Press the SHE reset button on the control panel (on the board). The red LED indicator on the automatic detector goes
out. The yellow LED indicator
yellow LED fl ashes indicating "OFF". The slider switch in the control panel should then be switched to the "active"
position. The yellow LED indicating
illuminated indicating "ON". The green LED indicator is illuminated indicating
Test buzzer / signal light
Slider switch is switched to the "secured" position. The yellow LED indicator
(fl ash code 5). On the TRZ Plus DG module the yellow LED fl ashes indicating "OFF". Press the red ON button
one of the SHE manual call points and the horn or indicator light connected to it will be triggered. The red LED indicator
- SHE activated - illuminates at all SHE manual call points. The horn / indicator light will deactivate after 3 minutes
SHE activation continues.
Completion work
Insert glass panes in all SHE manual call points. Close the control panel door. Stick on the service contact telephone
number.
Note: Start up procedure with batteries with less than the minimum voltage switch-off mains.
Disconnect battery fuse. Please wait for a minimum of 2 minutes. Switch on mains. Plug in battery fuse and
please close the control panel door. If the trial run fails, replace batteries and please repeat the Start up procedure and
trial run procedure.
40
indicating "unit functioning properly" goes out. The
OK
or N
gas) is released. On the TRZ Plus DG module the
2
2
fl ashes indicating "malfunction" (fl ash code 5). On the TRZ Plus DG module the
"malfunction" goes out and on the TRZ Plus DG module the green LED is now
- "ready for operation".
OK
fl ashes indicating "malfunction"
on