1.2 Type indication
Type
Klimat 15-15
Klimat 15-20
Klimat 20-20
Klimat 25-20
Klimat 30-20
Klimat 35-25
Klimat 35-35
Klimat 40-35
1.3 General warnings
Incorrect installation, adjustment, alteration, maintenance activity or repair may lead to material
or environmental damage and/or injuries. The appliance should therefore be installed, adapted
or converted by a skilled and qualified installer, taking into account national and international
regulations. Faulty installation, adjustment, alteration, maintenance activity or repair shall render
the warranty void.
1.4 Safety
The air treatment unit must be fitted with a lockable isolator switch (not supplied as standard).
Always disconnect the appliance from the mains when carrying out maintenance or repairs.
The motor and fan take some time to stop after the voltage has been switched off. Wait for at
least two minutes before opening the fan doors. Always comply with national and/or regional
regulations.

2.0 Positioning the appliance

On receipt, check immediately that the supply had been delivered in full. Check also for any
damage caused during transportation. If what is delivered does not comply with the goods
indicated on the packing list, and/or damage during transportation is recorded, the recipient must
state this on the delivery note indicating the date of receipt. If the recipient fails to comply with
the requirements above, he shall have no right to claim.
2.1 Assembly [15] [16] [17]
To avoid contact noise, we recommend that the air handling unit be placed on a level, vibration-
free floor or roof structure. The roof structure must be sufficiently stable, and must have
enough load-bearing points to prevent the air handling unit from bending. The air handling unit
must be attached to the roof structure. The unit must be placed on a level surface to ensure
that any condensation is properly drained off. Air handling units incorrectly installed can cause
the inspection doors in the unit to jam and possibly result in the unit leaking. With units with
a condensation extractor, the height of the installation structure must be at least the same,
or higher, than the required siphon height. Note: if the air treatment unit replaces the roof in
the location where it is installed, the manufacturer must be aware of this in advance so that
appropriate measures may be applied.
4
Dimensions (mm)
975x975
975x1280
1280x1280
1530x1280
1890x1280
2195x1530
2195x1530
2508x2195