Herunterladen Inhalt Inhalt Diese Seite drucken

Safety Intructions - STG-BEIKIRCH M3/...-500N:250N/LA/AC Bedienungsanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Safety intructions

Please observe the following safety instructions
which are emphasized by special symbols.
Caution: Danger to persons due to electricity.
Warning: Non-observance leads to destruction.
Danger to material due to incorrect handling.
Attention: Danger to persons due to risks arising from
the operation of the equipment. Danger of crushing/
trapping.
INFO
Warning 230 V AC: Dangerous voltage. Can cause death, serious injury or
considerable material damage. Disconnect the equipment from the power supply
at all poles before opening, assembling or carrying out any structural alterations.
Observe VDE 0100 for 230 V power connection.
Please observe the following for assembly and operation: the window closes
automatically. When opening and closing, the drive unit is stopped by the power
cut-off. The corresponding pressure force is listed in the technical data. Take care
- the pressure force is high enough to crush your fingers. During assembly and
operation, do not interfere with the window gap or the travelling drive! Danger of
crushing/trapping!
Operating instructions: for professional assembly, installation and appropriate
maintenance by trained, qualified and safety-conscious electricians and/or skilled
staff with knowledge of electrical equipment installation. Read and observe the
information contained in these operating instructions and respect the order of pro-
cedure stated therein. Please keep these operating instructions for future reference
and maintenance. Reliable operation and the prevention of damage and risks are
only granted if the equipment is assembled carefully and the settings are carried
out according to these instructions and to the operating instructions of the drives.
Please observe the exact terminal assignment, the minimum and maximum power
ratings (see technical data) and the installation instructions.
Application range: Exclusively for the automatic opening and closing of the stated
types of windows. For further application, please contact the manufacturer. It would
be beyond the scope of these safety instructions to list all the valide regulations
and guidelines. Always make sure that your system corresponds to the valid
regulations. Pay particular attention to: the aperture cross-section of the window,
the opening time and opening speed, the temperature resistance of the cables and
equipment, cross-sections of the cables in relation to the cable lengths and power
consumption. Required mounting material is to be adapted to the frame and the
corresponding load and is to be completed, if necessary. Any supplied mounting
material is only part of the required amount.
Maintenance works: If the equipment is employed in smoke heat extraction sys-
tems (in short SHE), they must be checked, serviced and, if required, repaired at
least once per year. This is also recommended for pure ventilation systems.
Free the equipment from any contamination. Check the tightness of fixing and
clamping screws. Test the equipment by trial run. The gear system is maintenance
free. Defective equipment must only be repaired in our factory. Only original spare
parts are to be used. The readiness for operation has to be checked regularly. For
this purpose a service contract is recommended.
04/24999913
Linear drive M3/...-500N:250N/LA/AC
All batteries provided with the SHE control panel need to be regularly checked as
part of the maintenance programme and have to be replaced after their specified
service life (approx. 4 years). Please observe the legal requirements when dispo-
sing of hazardous material - e.g. batteries.
Routing of cables and electrical connections only to be done by a qualified electri-
cian. Power supply leads 230 V AC to be fused separately by the customer. Keep
power supply leads sheathed until the mains terminal.
DIN and VDE regulations to be observed for the installation: VDE 0100 Setting up
of high voltage installations up to 1000 V. VDE 0815 Installation cables and wires.
VDE 0833 Alarm systems for fire, break-in and burglary.
Cable types to be agreed with local inspection authorities, power utilities, fire
protection authority and the professional associations.
All low voltage cables (24 V DC) to be installed separately from high voltage
cables. Flexible cables must not be plastered in. Provide tension relief for freely
suspended cables. The cables must be installed in such a way that they cannot
be sheared off, twisted or bent off during operation. Junction boxes must be
accessible for maintenance work. Adhere to the type of cables, cable lengths and
cross-sections as stated in the technical information.
The supply voltage and the batteries are to be disconnected at all
poles before maintenance work or structural alterations. The system
must be protected against unintentional re-starting. Electrical controls must be
voltage free before extension modules are taken off or added (disconnect mains
voltage and batteries).
After installation and any changes to the system check all functions by a trial run.
During assembly and operation, please observe: the windows may close automati-
cally. Potential crushing and cutting points between the casement and the window
frame, dome lights and support frame must be secured up to a height of 2.5 m
by safety equipment, which if touched or interrupted by a person will immediately
stop the movement (guideline for power operated windows, doors and gates of the
professional association).
Warning! The drives and call points are built for 230 V!
Risk of death!
For applications: Tilt windows: A scissor-type safety catch is to be installed.
It prevents damage caused by incorrect assembly and handling. Please
observe: the scissor-type safety catch must be adapted to the opening
stroke of the drive unit, i.e. that the opening of the safety catch must be
larger than the drive unit stroke in order to prevent blocking. See guideline
for power-operated windows, doors and gates. Provide all aggregates with
durable protection against water and dirt!
Attention: The control must only be operated with drives made by the
same manufacturer. No liability will be accepted and no guarantee nor
service is granted if products of outside manufacturers are used. Assembly and ins-
tallation must be carried out properly, according to the information of the operating
instructions paying particular attention to safety aspects. If spare parts, dismantled
parts or extension components are required or desired, only use original spare
parts.
Manufacturer's declaration: The equipment has been manufactured and tested
according to the European regulations. A corresponding manufacturer's declaration
has been submitted. You may only operate the system if a Declaration of Conformi-
ty exists for the entire system.