Room thermostat Basicline H 230 V
manual
1. Application
The electronic Basicline H 230 V room thermostat for the
room temperature-dependent regulating of heating
equipment is designed for use in dry closed areas.
2. Function
The internal temperature sensor
measures the room temperature.
The rotary button • is used to set
the desired room temperature to
a value within the range 5 °C to
30 °C (scale-digits 1-6). The
internal light-emitting diode ‚
indicates that the heating is
switched on.
An input allows the setpoint to be lowered using a
suitable control device (clock thermostat) or an external
clock.
2.1 Heating
The output is triggered when the room temperature falls
below the set setpoint. The active lowering reduces the
setpoint by approximately 2 K.
3. Installation — only by authorized trained personnel
Connection errors can cause damage to the automatic
control device!
No responsibility will be taken for any damage
resulting from the incorrect connection and/or
improper use!
>
The device must be disconnected from the mains
before any work is done on it.
>
Only authorized trained personnel may make the
connection and perform service!
>
Devices with safety extra-low voltage (SELV)
must not be connected.
>
The connection must be made using the
accompanying block diagram.
>
The same phase must be used for the power
supply (terminal 2) and the lowering (terminal 5).
>
The device is designed only for connection to
permanent wiring in dry closed areas.
>
The VDE 0100, EN 60730 (Part 1) and the regulations
of the local power utility company must be observed.
>
The automatic control device must be installed so that
it measures the average room temperature (avoid the
vicinity of inlet and outlet channels, windows and
doors). Install on interior walls approximately 1.3 to
1.5 m above the floor (avoid direct sunshine).
If the device does not function, first check the correct
connection and the power supply.
4. Technical data
Type:
Temperature range:
Sensor tolerance:
Switching difference:
Sensor:
Desired temperature setting: Exterior rotary button
Operating voltage:
Output:
Maximum permitted
switching current:
Electrical connections:
Method of operation:
Impulse voltage withstand level :2.5 kV
Pollution degree:
Perm.ambient temperature:
Housing:
Dimensions:
Mounting:
Cable routing:
Degree of protection:
Safety class:
Weight:
5. Dimensions (mm)
6. Connection diagram
Subject to change without prior notice
Basicline H 230 V
+5 to + 30 °C
±1 K
±0.2 K fixed
Internal NTC semiconductor
sensor
230 V AC / 50 Hz (±10 %)
Triac output with potential
0.8 A, 230 V AC
(resistive/max. 5 actuators)
Strip terminals
1.C (no limiter method of
operation)
2
0 to +40 °C
Material Upper part ABS/PC
(impact-resistant,
flame-protected)
Lower part: PA6 GF30
81 x 81 x 16 (25) mm
With flush-mounting box
Through flush-mounting box
IP 30
II
Approx. 90 g