Herunterladen Inhalt Inhalt Diese Seite drucken

Rittal CMC III Installationsanleitung Und Kurz-Bedienungsanleitung Seite 8

Can-bus access
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Service
Display of the status change:
– The two green and the two red CAN bus LEDs on the CAN bus connection flash.
EN
– The multi-LED of the Processing Unit flashes continually in the green – orange – red sequence.
– The multi-LED of the CAN bus access flashes blue continuously.
• Press the "C" key on the CMC III PU (a first audio signal is issued) and keep it pressed for approx.
3 seconds until a second audio signal is issued.
Display of the status change on the CAN bus LEDs:
– Green LEDs light continuously: CAN bus status "OK".
– Red LEDs light continuously: CAN bus status faulty.
Display of the status change on the multi-LED of the Processing Unit.
– Continuous green light: All units attached to the CAN bus have the "OK" status.
– Continuous orange light: At least one unit attached to the CAN bus has the "warning" status.
– Continuous red light: At least one unit attached to the CAN bus has the "alarm" status.
Display of the status change on the multi-LED of the CAN bus access:
– Continuous blue flashing: Communication over the CAN bus.
– Green flashing: When the measured value changes or, at the latest, every 5 seconds.
– Continuous red flashing: The CAN bus access has the "open" status.
– Continuous red light: Invalid measured value.
If the installation is not successful: see Section 1.1.
Note:
Connection cables in various lengths can be obtained from Rittal.
5.3
Settings
The following parameters can be set or viewed at the CMC III PU web site:
– Value: The current value of the access sensor (0 = door closed, 1 = door open)
– Sensitivity: Distance of sensor from door (1=small, 3=large)
– Delay: Status message delay [s]
– Status: Current status of the access sensor taking account of the delay value
Similarly, the parameters of the connected accessory can be set from the CMC III PU web site (see
Section 1.1).
To determine whether any software updates are required: see www.rittal.com or contact Rittal Service
(see Section 6).
6
Service
For technical questions, please contact:
Tel.: +49 (0) 2772/505-9052
E-mail: info@rittal.de
Homepage: www.rittal.com
For complaints or service requests, please contact:
Tel.: +49 (0) 2772/505-1855
E-mail: service@rittal.de
7
Rittal CMC III CAN-Bus Access

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Dk 7030.200

Inhaltsverzeichnis