Submenu: Switch-on conditions
Contents of
Options
submenu
Switch-on delay
Switch-on delay
Short interruption
Voltage window
Monitoring
Minimum
Maximum
Frequency window
Monitoring
Minimum
Maximum
Submenu: General settings
Contents of submenu
Language
Display
Password
Load settings
Save settings
Information
Submenu: Error memory
Contents of submenu
Error list
Error recording
Reset error memory
Operating counter
Cumulated OFF-time
Configuration possibilities
[1.00] - [600.00] s
[disabled], [enabled]
[disabled], [enabled]
[0.100] - [1.000] x U
[1.000] - [1.300] x U
[disabled], [enabled]
[45.00] - [60.00] Hz
[50.00] - [65.00] Hz
Options
Language
Switch-off delay
Contrast
Protection
Change password
"Setting name"
„Setting name"
Options
Remote trip
Power OFF
Step size
0.01 s
0.005 x U
n
0.005 x U
n
0.01 Hz
0.01 Hz
Configuration possibilities
[English], [Deutsch]
[10] - [600] s
[0] - [9]
[disabled], [enabled]
[****]
Configuration possibilities
[disabled], [enabled]
[disabled], [enabled]
VDE-AR-N 4105
BDEW
60 s
60 s
enabled
disabled
enabled
disabled
0.85 x U
0.95 x U
n
n
1.1 x U
1.2 x U
n
n
enabled
disabled
47.5 Hz
47.5 Hz
50.05 Hz
50.05 Hz
n
n