Herunterladen Inhalt Inhalt Diese Seite drucken

ABB CM-UFD.M31 Betriebs- Und Montageanleitung Seite 14

Netzeinspeiseüberwachungs relais; cm serie
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Submenu: Monitoring functions
Contents of
Options
submenu
Overvoltage >U
Monitoring
AV
Threshold value
Hysteresis
Overvoltage >U1
Monitoring
Threshold value
Hysteresis
Tripping delay
Overvoltage >U2
Monitoring
Threshold value
Hysteresis
Tripping delay
Undervoltage <U1
Monitoring
Threshold value
Hysteresis
Tripping delay
Undervoltage <U2
Monitoring
Threshold value
Hysteresis
Tripping delay
Overfrequency >F1
Monitoring
Threshold value
Hysteresis
Tripping delay
Overfrequency >F2
Monitoring
Threshold value
Hysteresis
Tripping delay
Underfrequency <F1
Monitoring
Threshold value
Hysteresis
Tripping delay
Underfrequency <F2
Monitoring
Threshold value
Hysteresis
Tripping delay
ROCOF
Monitoring
Threshold value
Number of cycles
Tripping delay
Error time
Vector shift VS
Monitoring
Threshold value
Error time
Configuration possibilities
[disabled], [enabled]
[1.000] - [1.300] x U
n
[0.1] - [10.0] %
[disabled], [enabled]
[1.000] - [1.300] x U
n
[0.5] - [10.0] %
[0.06] - [600.00] s
[disabled], [enabled]
[1.000] - [1.300] x U
n
[0.5] - [10.0] %
[0.06] - [600.00] s
[disabled], [enabled]
[0.100] - [1.000] x U
n
[0.5] - [10.0] %
[0.06] - [600.00] s
[disabled], [enabled]
[0.100] - [1.000] x U
n
[0.5] - [10.0] %
[0.06] - [600.00] s
[disabled], [enabled]
[50.00] - [65.00] Hz
[0.05] - [4.00] Hz
[0.06] - [600.00] s
[disabled], [enabled]
[50.00] - [65.00] Hz
[0.05] - [4.00] Hz
[0.06] - [600.00] s
[disabled], [enabled]
[45.00] - [60.00] Hz
[0.05] - [4.00] Hz
[0.06] - [600.00] s
[disabled], [enabled]
[45.00] - [60.00] Hz
[0.05] - [4.00] Hz
[0.06] - [600.00] s
[disabled], [enabled]
[0.100] - [5.000] Hz/s
[4] - [50]
[0.06] - [600.00] s
[0.50] - [600.00] s
[disabled], [enabled]
[2.0] - [40.0] °
[0.50] - [600.00] s
Step size
VDE-AR-N 4105
enabled
0.005 x U
1.1 x U
n
n
0.1 %
0.1 %
enabled
0.005 x U
1.15 x U
n
n
0.1 %
1 %
0.01 s
0.1 s
disabled
0.005 x U
1.15 x U
n
n
0.1 %
1 %
0.01 s
0.1 s
enabled
0.005 x U
0.8 x U
n
n
0.1 %
1 %
0.01 s
0.1 s
disabled
0.005 x U
0.8 x U
n
n
0.1 %
1 %
0.01 s
0.1 s
enabled
0.01 Hz
51.5 Hz
0.01 Hz
0.1 Hz
0.01 s
0.1 s
disabled
0.01 Hz
51.5 Hz
0.01 Hz
0.1 Hz
0.01 s
0.1 s
enabled
0.01 Hz
47.5 Hz
0.01 Hz
0.1 Hz
0.01 s
0.1 s
disabled
0.01 Hz
47.5 Hz
0.01 Hz
0.1 Hz
0.01 s
0.1 s
disabled
0.005 Hz/s
1 Hz/s
1
50
0.01 s
0.1 s
0.01 s
30 s
disabled
0.1 °
10 °
0.01 s
30 s
BDEW
disabled
1.1 x U
n
0.1 %
disabled
1.15 x U
n
1 %
0.1 s
enabled
1.2 x U
n
1 %
0.1 s
enabled
0.8 x U
n
1 %
2.4 s
enabled
0.45 x U
n
1 %
0.3 s
enabled
51.5 Hz
0.1 Hz
0.1 s
disabled
51.5 Hz
0.1 Hz
0.1 s
enabled
47.5 Hz
0.1 Hz
0.1 s
disabled
47.5 Hz
0.1 Hz
0.1 s
disabled
1 Hz/s
50
0.1 s
30 s
disabled
10 °
30 s
14

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis