Herunterladen Inhalt Inhalt Diese Seite drucken

Mitsubishi Heavy Industries PAC-MK31BCB Installationshandbuch Seite 12

Air-conditioners indispensable optional parts branch box
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 15
8. Electrical work
Total operating current of the indoor unit
F0 = 16A or less *
F0 = 5A or less *
F0 = 3A or less *
Apply to IEC61000-3-3 about max. permissive system impedance.
*1 The Ground-fault interrupter should support inverter circuit.
The Ground-fault interrupter should combine using of local switch or wiring breaker.
* Please take the larger of F1 or F as the value for F0.
F1 = Total operating maximum current of the indoor units × 1.
F = (V1/C)
Connect to Branch box (PAC-MK•BC)
Indoor unit
Type 1
SEZ-KD•VA, PCA-RP•KAQ, PLA-ZRP•BA(.UK)
Type 
PEAD-RP•JAQ(L).UK
Type 3
MLZ-KA•VA, SLZ-KA•VAQ(L)3
MSZ-FH•VE, MSZ-SF•VE, MSZ-EF•VE, MSZ-SF•VA,
Type 4
MSZ-GF•VE
Type 5
MFZ-KJ•VE, MSXY-FJ
Type 6
Branch box (PAC-MK•BC)
Type 7
ecodan C generation*5
*This value may increase due to a locally connected actuator.
C : Multiple of tripping current at tripping time 0.01s
Please pick up "C" from the tripping characteristic of the breaker.
Condition: Branch Box ×  + SEZ-KD•VA × 5, C=8 (refer to right sample chart)
F = 5.1 × /8 + 19.8 × 5/8
= 13.65
*3 Current sensitivity is calculated using the following formula.
G1 = V + V3 × (Wire length[km])
G1
Current sensitivity
30 or less
30 mA 0.1sec or less
100 or less
100 mA 0.1sec or less

Wire thickness (mm
)
1.5
.5
4.0
When connecting 3 units of the PLA-ZRP series respectively to the Branch Box
1.5mm

using 0m of wiring and connecting the Branch Box and PEFY-VMA to
a single breaker using wiring totaling 100m in length;
G1 = .4 × 3 + 3 + 1.6 + 48 × 0.0 × 3 + 56 × 0.1
= 0.8
→ 30 mA Current sensitivity
*5 When the ecodan is connected, the master controller (G-50A etc.) cannot be connected.
Warning:
In case of A-control wiring, there is high voltage potential on the S3 terminal caused by electrical circuit design that has no electrical insulation between power
line and communication signal line. Therefore, please turn off the main power supply when servicing. And do not touch the S1, S2, S3 terminals when the power
is energized. If isolator should be used between outdoor unit and branch box/indoor unit and branch box, please use 3-pole type.
*Power supply from Outdoor unit
L
Power supply
N
*Supply power separately to branch box and outdoor unit
L
Power supply
N
Caution:
After using the isolator, be sure to turn off and on the main power supply to reset the system. Otherwise, the outdoor unit may not be able to detect the
branch box(es) or indoor units.
1
Minimum wire thickness (mm²)
Main cable
Branch
1.5
1.5
.5
.5
4.0
4.0
Connect to Connection kit (PAC-LV11M)
V1
V
Indoor unit
19.8
MSY-EF•VE, MSY-GE•VA, MSY-GH, MSZ-GE•VA,
Type 1
MSZ-SF•VA, MSZ-SF•VE, MSZ-EF•VE, MSZ-FH•VE
6.9
Type 
MFZ-KJ•VE
9.9
.4
Type 3
Connection kit (PAC-LV11M)
6.8
7.4
5.1
3.0
5.1
5.0*
V3
48
56
66
L
L
Isolator (Switch)
Outdoor unit
N
N
L
L
Isolator (Switch)
Branch box
N
N
Capacity (A)
Fuse (A)
Ground
1.5
16
.5
5
4.0
3
V1
6.8
7.4
3.5
2 pole isolator
(Switch)
L
B1
Branch box
B2
N
3 pole isolator
(Switch)
S1
S1
S2
"A-control
S2
Indoorunit"
S3
S3
Breaker for wiring
Ground-fault interrupter *1
(NFB)
16
0
0A current sensitivity *3
5
30
30A current sensitivity *3
3
40
40A current sensitivity *3
V
Indoor unit
PMFY-VBM, PLFY-VBM, PEFY-VMS1, PCFY-VKM
Type 1
PKFY-VHM, PKFY-VKM, PFFY-VLRMM, PFFY-VKM
.4
Type  PLFY-VCM
Type 3 PKFY-VBM
Type 4 PEFY-VMA
PLFY-VLMD, PEFY-VMH,PEFY-VMR, PDFY-VM
Type 5
PFFY-VLEM, PFFY-VLRM, PWFY-VM
Sample chart
6000
600
60
10
1
0.1
0.01
1
2
Rated Tripping current (x)
3 pole isolator
(Switch)
S1
S1
S2
"A-control
S2
Indoor unit"
S3
S3
V1
V
19.8
.4
9.9
3.5
38.0
1.6
0
0
SAMPLE
3
4
6
8
10
20
C

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Pac-mk51bcb

Inhaltsverzeichnis