Heizkreis / Heating circuit QM
3. Certification & Labeling
Manufacturer:
Type:
EC-Type Examination
Certificate:
Labeling:
Heating circuits assembled by Quintex will be labeled and delivered by Quintex with all
specific data of the corresponding heating circuit.
Heating circuits which are assembled by the installer on site must be labeled clearly by the
installer using enclosed UV-resistant marker (Staedler Lumocolor) according to the
following example. The label of the heating circuit has to be mounted visible on the power
supply cable.
Only the following supply cables are allowed to use to assemble an Ex-certificated heating
circuit. For heating circuits QM6: Type Radox125-3x1,5 or Radox125-3x2,5
Power output:
e.g. 12 = 12W/m at 10°C
Heating cable type:
1 = ILL
CT/CF
2 = ILLw CT/CF
3 = ILM
CT/CF
4 = ILMP CT/CF
Ambient-/work piece temperature range
Version with terminal block (K)
heating cables with CT-outer jacket -40°C bis +65°C
heating cables with CF-outer jacket -20°C bis +85°C
Version with insulation sleeves (Q)
heating cables with CT-outer jacket -25°C bis +85°C
heating cables with CF-outer jacket -20°C bis +85°C
Quintex GmbH
QM_-_ _1-_2-_ _ _/K
QM_-_ _1-_2-_ _ _/Q
EPS 09 ATEX 1234X
II 2G Ex mb IIC T6/T5/T4
Power supply cable:
1 = 3G 1,5mm² Radox 125
2 = 3G 2,5mm² Radox 125
Length heating circuit in
m/DM
001 =
1m
DM1 = 0,1m
010 = 10m
DM5 = 0,5m
200 = 200m
DM9 = 0,9m
Power output:
e.g. 12 = 12W/m at 10°C
Length of heating circuit in
in m e.g.
1 =
1m
2 =
2m
10 =
10m
100 = 100m
Temperature class
ILL up to 23 W/m
= T6
ILL 31 W/m
= T4
ILLw
= T4
ILM / ILMw up
to 45 W/m
= T4