5.1.2
Switch point
The switch point (A) on the sensor depends on the orientation of the point level switch (water
+25 °C (+77 °F), 1 bar (14.5 psi).
A
 15
Vertical and horizontal orientation, dimensions in mm (in)
5.1.3
Viscosity
Switching delays may occur in the case of highly viscous liquids. Ensure that the liquid can
easily run off the tuning fork:
• If installing in vessels with high-viscosity liquids (A), the tuning fork may not be located in
the installation socket!
• If installing in vessels with low-viscosity liquids (B), the tuning fork may be located in the
installation socket!
• The installation nozzle must be no less than the minimum diameter of 50 mm (2.0 in).
A
 16
Installation options with consideration given to the liquid viscosity, dimensions in mm (in)
A
High viscosity (< 10 000 mPa·s)
B
Low viscosity (< 2 000 mPa·s)
Endress+Hauser
A
B
Installation
A
A0020734
A0022054
47