tant to choose an installation location free of conditions that could influence the
measurement such as direct sun light, too close occupant proximity, air flow
coming from windows or doors or ventilation systems.
EN
The front cover is opened with a tool pressing both pressure closures located at
both edges of the cover (see Fig.5). For safety reasons, cables must be retained
using the support provided (see Fig.6).
In the case of an installation where cabling is outdoors, it must be installed inside a
cable ducting system with IP4X protection degree classified as "cable ducting with
access cover that can only be opened with a tool" according to UNE-EN 50.085-1:
Cable trunking systems and cabling ducting systems for electrical installations-
Part 1: General requirements.
START UP
Pairing
See the instructions of the NARAH 160 RT energy recovery unit for the steps to
follow for pairing.
The 2-minute pairing window begins when the previously mentioned energy re-
covery unit is powered on. The AIRSENS RF.2 transmitter may remain powered at
all times to be paired. Once the pairing window has ended, pressing the S2 button
on the AIRSENS RF.2 (see Fig. 1) triggers 5 flashes on the LED D17 if the sensor is
within RF range and paired with the receiver.
If there is no response when pressing the button, it indicates that the device is out
of range or not paired.
Operating modes (see Fig.2)
MF1: Relay + Modbus (reading) – [SW1-3=OFF]
Adjustable relay via P1 potentiometer. Factory settings: 1200 ppm / 70%HR
MF2: 0-10Vdc output analogue signal + Modbus (reading) – [SW1=ON, SW2-3=OFF]
0-10Vdc output analogue signal adjustable via P1 potentiometer. Factory set-
tings: 1200 ppm / 70%HR
MF3: 2-10Vdc output analogue signal + Modbus (reading) – [SW1-2=ON, SW3=OFF]
2-10Vdc output analogue signal adjustable via P1 potentiometer. Factory set-
tings: 1200 ppm / 70%HR
MF4: Modbus control – [SW1-3=ON]
Access to reading, edition and communication of working parameters via Mod-
bus communication protocol (see Table 1, Modbus registers). Relay and output
analogue signal enabled. Factory settings: 1200 ppm / 70%HR.
Note: If another switch combination is chosen, LED diffuser is switched off and