Herunterladen Inhalt Inhalt Diese Seite drucken

Pinning Of The Profibus Port - Siemens SIMATIC NET CP 5613 A2 Produktinformation, Installationsanleitung

Kommunikationsprozessor
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

4.2

Pinning of the PROFIBUS Port

What is the pinning of the PROFIBUS interface (D-sub female connector)?
Pin
No.
1
2
3
4
5
6
7
8
9
Shield
Product Information/Installation Instructions CP 5613 A2, CP 5614 A2
A5E00779184
Product Information/Installation Instructions CP 5613 A2, CP 5614 A2
Abbreviation
NC
NC (M24)
RxD/TxD-P
RTSAS
M5
P5
NC (P24V)
RxD/TxD-N
RTS
Meaning
Not Connected
Not Connected
With other PROFIBUS compo-
nents, the return wire of the
floating 24 V power supply can
be applied to this pin.
Signal line B of the module
Control signal in diagnostic op-
eration
The control signal is high active
when the PLC is sending.
5 V ground – return wire (GND)
of the 5 V power supply.
The current load of an external
consumer connected between
P5 and M5 can be up to a
maximum of 90 mA.
Plus 5 V – 5 V supply.
The current load caused by an
external consumer connected
between P5 and M5 must not
exceed a maximum of 90 mA
(short-circuit proof).
Not Connected
With other PROFIBUS compo-
nents, the P24V pin of the 24 V
floating power supply can be ap-
plied to this pin.
Signal line A of the module
The control signal is high active
when the device (PG or PC) is
sending.
On connector housing
Input/Output
-
-
Input/output
Input
Output
Output
-
Input/output
Output