Mounting the control panel
The control panel must not be installed in a chamber. It should be accommodated either in a dry walkway behind
the pool wall or in an adjacent room. The connection must be effected carefully in accordance with EN 60335-2-
41. Connection to the power supply is effected by means of a 5 x 2,5 mm² (3N PE 400V) cable or a 4 x 2,5 mm² (3
PE 230 V) cable. Both a power switch, with which the unit can be isolated from the power supply on all poles, and
an earth leakage circuit breaker (R.C.C.B.) should be provided in this cable (see: "Information for the Electrician").
Plug the 10 m length of the PVC tube coming from the wall niche, onto the free nipple of the "T" connector (19
outside the control panel (18.
8
7
6
5
4
10
3
9
15
14
13
12
11
21
Install the control panel
higher than the water level
16
17
18
19