To calculate the length of the duct system you require, subtract the equivalent feet for each "Vent
piece" (Table Below) used in the system from the "Recommended maximum run" (Table Below).
The longest duct run that is acceptable (if completely straight) is 50 feet. The number of vent pieces
(elbow, transition, etc.) installed in your duct run will determine the maximum length the duct run can
be. Please refer to the example below:
Duct Run Calculation:
6" round duct
Each 90° elbow used
Each 45° elbow used
Each 6" to 3/14 x 10" transition
used
Side wall cap with damper
Roof cap
Power Rating
General Input Power
Levels Of Speed Control
Control Type
Illumination
Venting Size
CALCULATING VENT SYSTEM LENGTH
Recommended maximum run
Vent piece deduction
SPECIFICATIONS*
Duct Run Calcuation example:
50 ft
One roof cap, two 90° elbows, and one 45° elbow
used:
7ft + 9ft + 9ft + 5ft = 30ft used.
9 ft
The above vent pieces used are equivalent to 30ft
5 ft
of a straight duct run. Subtract 30ft from the al­
7 ft
lowable 50ft. The remaining distance of 20ft is the
longest that the straight ducting (in addition to the
7 ft
vent pieces) can be.
7 ft
110-120V/60Hz (USA & Canada standard)
206W+# of Light x Votage of Light
4 Levels
Touch/Gesture
LED 3W 12V
Top Vent, 6 inch Round