Wiring
STM-1160-0007 / STM-2160-0007
STM-1170-0007
D
__
_____________
T
__
_____________
P2
__
GND
__
P1/UB+
__
STM-2150-0005
S+
__
D
__
_____________
T
__
_____________
GND
__
STM-2190-0005
S+
__
P2
__
GND
__
P1/UB+
__
Setup and Adjustments
Wiring
To wire see the appropriate wiring diagram.
Note: Use 0.75 mm² diameter wire minimum. Do
not exceed 50 m between the controller and the
room unit.
AO
__
___________
Fan
S+
__
____________
passive sensor
D
__
_____________
Mode LED | 5 V
T
__
______________
Occupancy button
P2
__
____________
Remote setpoint
GND
__
_________
0 V⏊
P1/UB+
__
_____
Poti | 5 V =
Mode LED | 5 V
Occupancy button
___________
Remote setpoint
_________
0 V⏊
_____
Poti | 5 V =
____________
passive sensor
Mode LED | 5 V
Occupancy button
_________
0 V⏊
____________
passive sensor
____________
Remote setpoint
_________
0 V⏊
______
Poti | 5 V =
STM-11xx/ STM-21xx Series Room Module
_____________
←
Rotary switch
______________
←
Rotary switch
______________
←
Rotary switch
←
______________
Rotary switch
AUTO
________
←
Rotary switch
____________
→
max. 35..125 V ~ | 30 V =
STM-2160-0005
S+
__
D
__
T
__
______________
P2
__
GND
__
P1/UB+
__
Nominal Values for passive Sensors
Temperature
°C
NTC 10 kΩ
-35 °C
240.799,17
-30 °C
175.846,19
-25 °C
129.735,04
-20 °C
96.659,70
-15 °C
72.697,82
-10 °C
55.171,64
-5
42.234,41
0
32.600,00
+5
25.364,16
+10
19.885,33
+15
15.704,31
+20
12.489,62
+25
10.000,00
+30
8058,49
+35
6534,29
+40
5329,99
+45
4372,56
+50
3606,87
+55
2991,00
+60
2492,91
+65
2087,94
+70
1756,98
3
III
__
II
__
II
__
0
__
__
C
__
____________
passive sensor
_____________
Mode LED | 5 V
Occupancy button
____________
Remote setpoint
_________
0 V⏊
_____
Poti | 5 V =
Resistance Ω
NTC 2.252 Ω
54.541,86
39.788,79
29.330,5
21.838,32
16.415,73
12.452,88
9.529,11
7.353,01
5.718,95
4.482,16
3.538,79
2.813,65
2.252
1.814,21
1.470,58
1.199,17
983,43
810,95
672,24
560,09
468,93
394,46