en - Original instructions
CPA 01
EN
6.2 Wiring
Mode A2
Counter forward & Counter reverse
L1
CPA 01
CPA 01
L2
Mode A2
Mode A2
Mode A3
PLC/SCADA (+ voltage switched)
L1
CPA 01
CPA 01
L2
Mode A3
Mode A3
Mode A4
Counter (balanced)
L1
CPA 01
CPA 01
L2
Mode A4
6.3 Cable extension
The cable can be extended by the user up to 90 me-
tres. Recommended cable quality is: PUR/FEP
A4x24 AWG
4
L1
white
L2
yellow
GND
grey
CUT
red
+
+
+ Pulse
+ Direction
PLC
PLC
+
7 Overvoltage and Overcurrent
Protection
Transient voltage protection is highly recommended
for wiring outside buildings.
8 Parameterisation
The CPA 01 can provide different pulse values and
pulse lengths.
The required values can be programmed in the Cor-
donel flow meter by using a SIRT and the Diavaso
Config app. The CPA 01 adopts the values automati-
cally.
The pulse length must always be adjusted to the
max. expected flow rate and the programmed pulse
value.
The period of the high signal shall always be shorter
than the period of the low signal. The following table
shows the longest suitable pulse lengths in relation
to the maximum expected flow and the pulse value.
Flow
Pulse value [Litre]
rate
*)
*)
0.01
0.1
1
3
[m
/h]
max. Pulse length [ms]
1
10
100
500
2.8
5
50
500
5
1.5
20
200
10
1.5
10
100
15
—
10
100
20
—
5
50
25
—
5
50
30
—
5
50
40
—
1.5
20
50
—
1.5
20
60
—
1.5
20
70
—
1.5
20
80
—
1.5
20
90
—
1.5
10
100
—
1.5
10
125
—
—
10
150
—
—
10
175
—
—
10
200
—
—
5
250
—
—
5
300
—
—
5
400
—
—
1.5
500
—
—
1.5
600
—
—
1.5
700
—
—
1.5
800
—
—
1.5
10
100
1000
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
200
500
500
200
500
500
200
500
500
200
500
500
200
500
500
100
500
500
100
500
500
100
500
500
100
500
500
100
500
500
50
500
500
50
500
500
50
500
500
20
200
500
20
200
500
20
200
500
20
200
500
20
200
500