VEAB Heat Tech CV MODBUS Serie Handbuch Seite 24

Elektro-heizregister

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 6
CV ..-..-..MODBUS
Signal name
DO_CONF
DO1_CONF
DO2_CONF
DO3_CONF
DO4_CONF
DO5_CONF
DO6_CONF
DO7_CONF
MODBUS address
MODBUS parity
MODBUS stop bits
MODBUS speed
MODBUS T15
MODBUS T35
NoOfDigIn
NoOfDigOut
NoOfAnaIn
NoOfAnaOut
Type
MODBUS address
X, 3
46
X, 3
47
X, 3
48
X, 3
49
X, 3
50
X, 3
51
X, 3
52
X, 3
53
X, 3
54
X, 3
55
X, 3
56
X, 3
57
X, 3
58
X, 3
59
X, 3
60
X, 3
61
X, 3
62
X, 3
63
Default value
Description
-
Not used
Configuration for DO1:
0 = OFF, 2 = Pulse/Pause
5 = Normal Digital Out
5
With Offline Action:
128 = OFF, 130 = Pulse/Pause
133 = Normal Digital Out
Configuration for DO2:
0 = OFF, 2 = Pulse/Pause
5 = Normal Digital Out
2
With Offline Action:
128 = OFF, 130 = Pulse/Pause
133 = Normal Digital Out
-
Not used
-
Not used
-
Not used
-
Not used
-
Not used
For use with OJ Air2 Master
114
set to 113 or 114
0, 1, 2 = no, odd, even
2
Set with DIP-switch
0 = One stop bit
0
1 = Two stop bits
Set with DIP-switch
0, 1, 2 , 20 =
0
9600, 19200, 38400, 115200
Set with DIP-switch
3
MODBUS timing control
5
MODBUS timing control
2
Number of Digital Inputs
6
Number of Digital Outputs
3
Number of Analog Inputs
0
Number of Analog Outputs
24