Ostberg RKB EC Montageanleitung Seite 12

Inhaltsverzeichnis
Verfügbare Sprachen

Verfügbare Sprachen

F A U L T D E T E C T I O N
LED
Relays K1
Code (for function
factory setting)
3 x
De-energized, HALL-IC
terminals
11-14
interrupted.
4 x
De-energized, Line failure (only for 3 ~ types)
terminals
11-14
interrupted.
5 x
De-energized, Motor blocked
terminals
11-14
interrupted.
6 x
De-energized, IGBT Fault
terminals
11-14
interrupted.
7 x
De-energized, DC undervoltage
terminals
11-14
interrupted.
8 x
De-energized, DC overvoltage
terminals
11-14
interrupted.
9 x
Energized,
terminals
11-14
bridged.
Cause
Explanation
Incorrect signal from the Hall-ICs,
error in the commutation.
The device is provided with a built-in Following a shut off, a start up
phase-monitoring function for the
mains supply. In the event of a mains 15 seconds, if the voltage supply is
interruption (failure of a fuse or
mains phase) the unit switches off
after a delay (approx. 200 ms).
Function only when load for the con-
troller is high enough.
If after 8 seconds cummutation no
speed is measured > 0, the fault
"Motor blocked" is released.
Shortcut earth or shortcut of motor
winding.
If the voltage drops below a specified rises again within 75 seconds above
limit, the device is shut off.
If the voltage increases below a
specified limit, the motor is switched the limit, an automatic starting test
off. Reason for excessively high input is run. If the intermediate circuit
voltage or alternator motor operation. voltage remains above the limit for
IGBT cooling down period
IGBT cooling down period for
approx. 60 sec.
Final shut off after 2 cooling-off
intervals
Code 6.
Reaction of Controller
Controller turns the motor off.
Automatic restart if no more
fault is recongized.
attempt is made after approximately power
high enough.
This keeps occurringuntil all 3
supply phases are available again.
EC-Controller switches off, renewed Check if
attempt to start after about 2,5 sec.
Final shut off, when fourth starting
test fails. It is then necessary to have rotatable.
an enabling reset or to disconnect
the power supply.
EC-Controller switches off, renewed
attempt to start after about 60 sec.
Code 9. Final shutoff, if -
following a second starting test –
a second fault detection is detected
within a period of 60 seconds.
If the intermediate circuit voltage
the limit, an automatic starting test
is run. If the intermediate circuit
voltage remains below the limit
for more than 75 seconds, the device
is shut off with a fault message.
If the intermediate circuit voltage
drops again within 75 seconds below
more than 75 seconds, the device is
shut off with a fault message.
12
Adjustment
Checking
supply.
motor is
freely