F A U L T D E T E C T I O N
For fan type 500x250 E1 EC to RKB 1000x500 F3 EC.
Operating conditions are indicated by the status LED with flashing code.
All others have alarm relay only.
LED
Relays K1
Code (for function
factory setting)
OFF
De-energized, No line voltage.
terminals
11-14
interrupted.
ON
Energized,
terminals
11-14
bridged.
1 x
Energized,
terminals
11-14
bridged.
2 x
Energized,
terminals
11-14
bridged.
Cause
Explanation
Normal operation without fault.
Motor interlocked = OFF
Terminals "D1" - "24 V / 10 V"
(Digital In 1) not bridged.
Active temperature monitoring.
The device has an active temperature
monitoring to protect it from damage
caused by excessively high interior
temperatures.In case of a temperature
increase above the predetermined
threshold value, the level control is
linearly reduced. To prevent a shut
down during reduced operation by to
high temperature of the entire system
(in this operating mode, allowable for
the controller) no switch off an no
alarm indication occurs by the relay.
OFF
ON
1 x
2 x
3 x
4 x
5 x
6 x
7 x
8 x
9 x
Reaction of Controller
Line voltage available?
At sinking temperature the
modulation rises again llinear. of the controller.
11

Adjustment

Unit switches OFF
and automatically
ON when the vol-
tage has been
restored.
Connection
between "D1" and
"24V/10V" broken
by external contact.
Check cooling