To prevent danger an RCD or ELCB
has to be installed!
Caution:
To avoid external touching and damage, it is
required that within the application the
product (component) has to be covered by a
metal sheeting or braid, which has to be
included in the protective arrangement of
Protection Class I (protective earth) according
to VDE0100 or to the relevant standards in
your country and is to be taken into
consideration. Metallic components coming in
contact with the product have to be
incorporated in the protection measures of
Protection
Class I (protective earth). For details please
refer to the standard VDE 0100 (Germany) or
the relevant standards in your country.
Additional to these instructions special
requirements for the specific products are
found on the product label or type plate and
must be followed as well.
The products are designed at a certain
protection class. Considering that the product
is not protected against hazardous body
currents, it has to be installed in such a
manner that any risk is excluded.
In case of doubt or if necessary please contact
us. (see last page for contact information)
Operation
Prior to connection of the product, please
ensure that the supply voltage matches the
product
data
label
specifications
out
documents, respectively.
Any product must be temperature
controlled! (unless otherwise stated
or specified)
or
the
product
of
the
accompanied
When
connecting
requirements of the standards listed below in
"General Safety Instructions" and "Additional
Safety Instructions" have to be observed.
The maximum operating and withstand
temperature for the product is 200°C (392°F)
or 150°C (302°F) in case of designs with
adhesive foil. It has to be ensured that this
temperature is never exceeded at any point of
the product, irrespective of whether it is
switched on or off.
In cases in which the kind of installation or
application cannot exclude that the maximum
product temperature is exceeded, a suitable
device for temperature control and, if
necessary, for temperature limitation has to
be provided. Proper operation of the
temperature controlling and limiting devices
has to be checked at initial operation.
De-sizing:
Owing to technical reasons, some smoke or
vapors will develop on heating temperatures
>110°C during initial operation. This is caused
by the heat-up of the size (slipping / binding
or cross-linking agent). To avoid these effects
during operation the product should be
tempered once at maximum 200°C for up to 4
hours. The emerging vapors are harmful and
should not be inhaled.
Please permit good ventilation
during this de-sizing phase!
Maintenance and Safety
Maintenance
and
according to the standards listed under
"General Safety Instructions" and "Additional
Safety Instructions", the regulations of the
employer's liability insurance associations
applicable to the respective way of use, as
well as other relevant rules applying to the
application. The operation of the system
should be checked for correct functionality.
The electrical supply should be checked to
ensure it conforms to the system design
documentation.
the