6. Commissioning, operation
6. Commissioning, operation
Personnel: Skilled personnel
Tools: SW 27 open-ended spanner or torque wrench
EN
Only use original parts (see chapter 12 "Accessories").
Check the instrument for any damage that may have been caused.
Obvious damage must be reported to the manufacturer immediately.
WARNING!
Physical injuries and damage to property and the environment
caused by hazardous media
Upon contact with hazardous media (e.g. oxygen, acetylene, flammable
or toxic substances), harmful media (e.g. corrosive, toxic, carcinogenic,
radioactive), and also with refrigeration plants and compressors, there is a
danger of physical injuries and damage to property and the environment.
Should a failure occur, aggressive media with extremely high temperature
and under high pressure or vacuum may be present at the instrument.
▶
▶
The digital pressure gauge is designed for operation under the following ambient
conditions (IEC 61010-1):
Overvoltage category II, pollution degree 2
■
2,000 m [6,562 ft] above sea level
■
Use indoors or outdoors
■
Avoid exposure to the following factors:
Direct sunlight or proximity to hot objects
■
Mechanical vibration, mechanical shock (putting it down hard)
■
Soot, vapour, dust and corrosive gases
■
Hazardous environments, flammable atmospheres
■
Ambient temperature outside the temperature range for which the instrument is
■
suitable: -10 ... +50 °C [14 ... 122 °F] (non-condensing, non-freezing), without sudden
changes
Humidity: > 84 % r. h. (non-condensing)
■
Mounting near to electromagnetic switches or cables carrying high currents
■
Direct contact with water, oil, chemicals or their vapours
■
Installation and plant conditions which can lead to the formation of atomic hydrogen
■
in the connection channel of the sensor.
22
For these media, in addition to all standard regulations, the appropriate
existing codes or regulations must also be followed.
Wear the requisite protective equipment.
WIKA operating instructions, model CPG1200