8 Radio-controlled operation (EnOcean)
• Correct operation of a unit pair is monitored by
the master unit.
• Teach-in mode is deactivated each time a radio
component is saved, meaning that it has to be
called up again for each further component.
• If nothing is received within 120 seconds, the
teaching-in process is ended (the LED on the
ventilation unit switches off).
• Teach-in telegrams from non-supported units
are ignored.
8.3 Radio switch
The FWL-PushPull RLS-RC is a double rocker
radio switch for operating FWL-PushPull-45 RC /
FWL-PushPull-30 RC (TwinUnit) ventilation
units. The operating mode and ventilation level is
transferred to all taught-in FWL-PushPull-45 RC/
FWL-PushPull-30 RC (TwinUnit) master ventila-
tion units.
Basic state
Hold 2 sec.
3 LEDs
intervals
Teach-in mode
Press 1x
Press 2x
Press 3x
Press 4x
Basic state
8.6 Teaching-in radio devices
Receiver = FWL-PushPull-45 RC, FWL-Push-
Pull-30 RC (TwinUnit), FWL-PushPull RLS-
LTRC
Transmitter = FWL-PushPull-45 RC, FWL-
PushPull-30 RC (TwinUnit), FWL-PushPull
RLS-RC, FWL-PushPull RLS-LTRC
54 | Wolf GmbH
Telegrams of other
radio devices
Send-teach mode
Delete mode
Repeater mode
FWL-PushPull-45, FWL-PushPull-45 RC
8.4 FWL-PushPull RLS-LTRC
EnOcean extension module
The FWL-PushPull RLS-LTRC EnOcean exten-
sion module allows radio-controlled FWL-Push-
Pull-45 ventilation units to also be operated with
the wired FWL-PushPull RLS-K control. The
FWL-PushPull RLS-LTRC is connected to the
RS 485 interface of the FWL-PushPull RLS-K.
Note
The FWL-PushPull RLS-LTRC EnOcean module
can only be taught-in with the commissioning soft-
ware (FWL-PushPull RLS-K). This activates the
teaching mode and sends a radio telegram. All ra-
dio sensors/radio switches are taught-in directly
on the FWL-PushPull RLS-LTRC. Only the
EnOcean module is taught-in on the master.
→ Commissioning or Commissioning software.
8.5 Radio telegram program levels
Hold > 2
3 LEDs 1x short
sec.
Teach telegram is sent
Hold > 2
3 LEDs 1x long
sec.
Memory deleted
+ red LED 1x
Repeater – Off
Press 1x
+ red LED 2x
Repeater – Level 1
+ red LED 3x
Repeater – Level 2
The repeater function (signal amplification) is
available for EnOcean radio sensors and radio
switches with EEP protocol. No signal ampli-
fication is possible between the FWL-Push-
Pull-45 and FWL-PushPull-30 (TwinUnit) ventil-
ation units (internal unit protocol).
Hold > 2
sec.
Desired repeater level