Herunterladen Diese Seite drucken

Georg Fischer Piping Systems DSR 500-1 Betriebsanleitung Seite 37

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

1. Place the positioner on the mounting kit bracket. In doing so, the coupling must engage
in the slot in the actuator (A).
2. Fasten the positioner to the bracket using screws (4) and washers (5).
3. Never loosen the screw pins of the coupling (1) and the ring (2)!
4. Connect the pneumatic supply between the positioner and the actuator.
o For single-acting actuators: output Y1
o For double-acting actuators: outputs Y1 and Y2
Ensure that this connection is leak-tight, because otherwise the solenoid
valves in the positioner will operate constantly.
5. Open the cover on the positioner and provide the electrical connections.
6. Connect supply air (connection "P").
7. Adjust the positioner.
8. Close the cover on the positioner.
To remove the positioner, follow the same sequence in the reverse order.
2.11
The positioner can be equipped with auxiliary modules (e.g. analogous feedback).
These auxiliary modules are put on to the plug-in place on the connection circuit board.
Please gather the technical data from the operating instructions of the corresponding auxiliary
modules.
37
3
5
4
1
Additional Modules
6
2
A