SIMATIC
Industrial PC
SIMATIC IPC277E
Product Information
ATEX / IECEx / UL HazLoc / UKCA
Additional Instructions for use in Gas and Dust Explosive Atmospheres
Only valid for specific order codes (MLFB)
Marked with approval symbol on the nameplate of the device
Additionally to the installation instructions in the user manual of IPC277E the following specifications must be
observed for installation in hazardous locations. If there are differences between the user manual and this product
information (PI) the statements in the PI have higher priority.
ATEX approval
II3G
II3D
Standards:
EN IEC 60079-0:2018
EN 60079-7:2015 + A1:2018
EN 60079-31:2014
IECEx approval
Standards:
IEC 60079-0:2017 (Ed. 7)
IEC 60079-7:2017 (Ed. 5.1)
IEC 60079-31:2013 (Ed. 2)
UL HazLoc approval
CL I, DIV 2, GP. A,B,C,D,T4
CL I, Zone 2, GP. IIC, T4
Standard:
UL 61010-2-201
CAN/CSA No. 61010-2-201
UL 12.12.01 (Hazardous Location)
CAN/CSA C22.2 No. 213-17 (Hazardous Location)
Approval marks
DEKRA 15ATEX 0119 X and / or IECEx DEK 15.0080X and/or DEKRA21UKEX0209X for Gas
DEKRA 20ATEX0082 U and / or IECEx DEK 20.0041U and/or DEKRA21UKEX0210X for Dust
UL - E-file number: E223122
Permissible ambient temperature during operation for devices with Ex marking
Vertical installation in horizontal format
Inclined installation in horizontal format ± 45°
Vertical installation in upright format
SIMATIC IPC277E
A5E51267679-AD, 05/2022
Ex ec IIC T4 Gc
Ex tc IIIC Dc
Ex ec IIC T4 Gc
Ex tc IIIC Dc
With CFast or SSD
With CFast or SSD
With CFast or SSD
+0 to +45 °C
+0 to +45 °C
+0 to +40 °C