Herunterladen Inhalt Inhalt Diese Seite drucken

Electrical Wiring - Riello Gulliver 3736210 RG1RK 362 T1 Montageanleitung Und Bedienungsanleitung

Öl-gebläsebrenner
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

3.4 ELECTRICAL WIRING

WARNING
DO NOT EXCHANGE NEUTRAL WITH PHASE
~
50Hz 230V
PE L
N
Safety thermostat
7 pin plug
7 pole socket
D1912
Ignition
electrodes
CONTROL BOX (see fig. 9)
To remove the control-box from the burner, loosen screw (A) and pull
to the arrow direction, after removing all components, the 7 pin plug
and earth wire.
In case of disassembly of the control box, retighten the screw
(A) with a torque wrench setting of 1 – 1.2 Nm.
1885
Main switch
T6A
Limit thermostat
Brown
Blue
Black
White
Blue
Heater with start
Burner-earth
NOTES:
– Wires of min. 1 mm
otherwise by local standards and legislation).
– The electrical wiring carried out by the installer
must be in compliance with the rules in force in
the Country.
TESTING
Check the shut-down of the burner by opening
the thermostats and the lock-out by darkening
the photoresistance.
Hour counter
(230V - 0.1A max.)
Remote lock-out signal
(230V - 0.5A max.)
Photoresistance
Oil valve